Carefully inspect each item in the package for signs of damage. If damage 
is found, please contact Siemens Technical Support: 1.888.333.3545. 
For more information about this  product or other Siemens products, 
visit www.purgethesurge.ca.

Figure 2:  Dimensions and Weight

Figure 3:  Mounting options

• 

3/4” pipe nipple (conduit nut included)

• 

Standard 35mm DIN-rail (not included)
L-bracket tightens onto DIN-rail  

• 

Standard flat mounting surface
Attach L-bracket to surface via mounting holes

TPS3  03’s  have  demonstrated  200kA  Short  Circuit  Current  Ratings 
(SCCR)  including  leads  (120/240V  Split  phase  models  have  100kA 
SCCRs). See UL Label markings on SPD or see Data Sheet for specs.)  
Supplemental overcurrent protection is not required to protect this SPD. 
However, NEC® convention requires that connecting conductors have 
overcurrent protection in Type 2 or 4 applications. Follow applicable 
codes.

This  device  features  internal  overcurrent  and  overtemperature 
protection that will disconnect effected surge suppression components 
at the end of their useful life, but will maintain power to the load – now 
unprotected. If this situation is undesirable for the application, follow 
these instructions for replacing the device.  TPS3 03 is ultrasonically 
welded closed and contains no user serviceable parts.

Table 1:  Specifications

 

Specifications

Temperature Operating

-40

o

C (-40

o

F) to 60

o

C (+140

o

F)

Temperature Storage

-55

o

C (-67

o

F) to 65

o

C (+149

o

F)

Wire Size & Installation Torque

10 AWG; 18 inch-pounds

Appropriate Circuit Breaker
based on conductor size

30A (SPD includes internal OCP)

NEMA 250 Enclosure Rating

Type 4X with appropriate 
sealing & sealing condulets

Voltage Rating & Application

Before installing SPD, verify by nameplate voltage or model number 
that it has the same voltage rating as the power distribution system. 
If unsure, call Siemens Technical Support at 1.888.333.3545 before 
proceeding.  The  SPDs  specifier  or  user  should  be  familiar  with  the 
configuration and arrangement of the power distribution system. The 
system is defined by how the secondary windings of the transformer 
supplying  the  service  entrance  main  or  load  are  configured.  This 
includes whether or not the transformer windings are referenced to 
earth via a grounding conductor. The system configuration is not based 
on how any specific load or equipment is connected to a particular 
power distribution system. SPDs should be installed per the distribution 
system, not per a load or motor’s wiring connection.  

For  example,  suppose  a  480V  three  phase  motor  appears  to  be 
connected  as  a  480V  Delta.    In  actuality,  the  serving  distribution 
system  might  be  a  480Y/277V  grounded  Wye,  with  or  without  a 
neutral pulled to the motor or MCC. The system is still a 480Y/277V 
Wye, even though the load is connected as a Delta.  A grounded Wye 
has a defined reference to ground (i.e., neutral is bonded to ground).  
In  contrast,  some  Delta  systems  are  ungrounded,  which  have  no 
reference to ground.  

Table 2:  Model Number Decoder

Model

Voltage 

Code

System/Service Voltage

TPS3A03

A

240/120V 1Ø, 3W Plus Ground,

TPS3B03

B

240/120V 3Ø, 4W Plus Ground High Leg Delta 

TPS3C03

C

208Y/120V 3Ø, 4W Plus Ground

TPS3D03

D

240v 3Ø, 3W Plus Ground 

TPS3E03

E

480Y/277V 3Ø, 4W Plus Ground

TPS3F03

F

480v 3Ø, 3W Plus Ground 

TPS3G03

G

600v 3Ø, 3W Plus Ground 

TPS3K03

K

380Y/220V 3Ø, 4W Plus Ground 

TPS3L03

L

600Y/347V 3Ø, 4W Plus Ground 

TPS3S03

S

400Y/230V 3Ø, 4W Plus Ground 

SPDs on Ungrounded Systems

Caution  – 

Ungrounded  systems  are  inherently  unstable  and  can 

produce excessively high line-to-ground voltages during certain fault 
conditions.  During these fault conditions, any electrical equipment 
including an SPD, may be subjected to voltages which exceed their 
designed ratings.  This information is being provided to the user so 
that an informed decision can be made before installing any electrical 
equipment on an ungrounded power system.

3.26”

3.26”

1.15”

4.13”

3/4”-14

Sized for std 35mm DIN-Rail

3.31” 3.57”

Weight:  1.60 lbs

(0.73 kg)

Bracket Mount 

for flat surfaces

Std. 3/4”-14 Nipple

DIN-rail Mount

(rail not incl.)

Содержание TPS3 03

Страница 1: ...User Manual Canada TPS3 03 Surge Protective Device ...

Страница 2: ...age rating of the SPD and system must be verified before energizing the SPD Failure to follow these guidelines can lead to abnormally high voltages at the SPD This may cause the SPD to fail The warranty is voided if the SPD is incorrectly installed and or if the neutral conductor in the service entrance equipment or downstream of separately derived systems is not bonded to ground in accordance wit...

Страница 3: ...opriate safety precautions including Personal Protection Equipment Failure to follow these instructions can result in death serious injury and or equipment damage When used in outdoor applications customer must seal the conduit nipple using watertight fittings not included to ensure a watertight connection Read this manual in entirety prior to installing Figure 1 SPD Types 2008 NEC Art 285 UL 1449...

Страница 4: ...familiar with the configuration and arrangement of the power distribution system The system is defined by how the secondary windings of the transformer supplying the service entrance main or load are configured This includes whether or not the transformer windings are referenced to earth via a grounding conductor The system configuration is not based on how any specific load or equipment is connec...

Страница 5: ... visible 6 Mount SPD weather resistant applications require additional sealing o rings etc not included Remove an appropriately sized knockout from panel Connect conductors as appropriate short and straight as possible Hi Legs are Phase B 7 Label or mark conductors as appropriate neutral white ground green energized black hi leg orange 8 Make sure system is bonded per NEC and is clear of hazards o...

Страница 6: ... option monitors suppression element condition and is not intended for use as phase loss or phase detection monitoring Normal Operation Green LED Indicators Each phase s LED Indicator illuminates when the SPD is energized and operating correctly Every suppression element is monitored and connected by logic to the LED Should any suppression element fail the green LED will extinguish Form C Dry Cont...

Страница 7: ... return of any product Returned products must be sent to the factory with the transportation charges prepaid In addition the company also warranties unlimited replacement of modular and component parts within the warranty period previously described The company specifically disclaims all other warranties expressed or implied Additionally the company is not be responsible for incidental or conseque...

Страница 8: ...Siemens Canada Limited 1577 North Service Road East Oakville ON L6H 0H6 SPD Hotline 888 333 3545 info purgethesurge ca 4 11 13 lh 8226 ...

Отзывы: