DIMENSIONS AND WEIGHT
The TPS9 (all models) weight is 4 lbs.
123456
123456
123456
123456
3.00
1.50
1.08
Page 3
INSTALLATION WIRING DIAGRAMS
Figure 1
TPS9 Transient Voltage Surge Suppressor Installation
(typical)
Mounting Screws
(4 places, not supplied)
Wiring to Neutral or
Ground Bus:
Ground - Green
Neutral - White
(if used)
Outer Breaker Panel
Cover Screws
(6 places, typical)
Integral Chase Nipple
(nut installed)
Chase Nipple Nut
Wiring to Breaker:
Phase A - Black
Phase B - Black (Orange
if High-Leg Delta)
Phase C - Black
TPS9 TVSS
0
0
0
0
0
0
Distribution Equipment
Metal Wall of
Distribution Equipment
1234
1234
20 Amp
Breaker
Figure 2
Typical Parallel Connections
Breaker
Panel
Interconnecting Wiring:
•
Minimize Length
•
Avoid Sharp Bends
•
Gently Twist Conductors Together
CONDUCTING DIELECTRIC AND/OR HI-POTENTIAL
TESTING WILL CAUSE INTERNAL DAMAGE TO
TPS UNIT AND WILL VOID THE UNITS WARRANTY
Do not perform dielectric or high potential
tests with the TPS unit installed.
CAUTION
V
WARNING
•
Confirm XO N-G Bonding at Upstream Transformer
•
Do Not Hi-Pot Test TVSS
•
Resulting Damage is Not Covered Under Warranty
.
A
A
A
A
B
B
B
B
C
C
C
C
3.00"
2.21"
7.91"
7.41"
∅
.201"
TVSS Unit