Installation Instructions
Peligro
Tensión peligrosa
Puede causar daños serio o la
muerte.
Desenergice totalmente antes de
instalar o darle servicio.
Reemplace todas las barreras y
cubiertas antes de energizar el
interruptor.
Instructivo de Instalación y Operación
Hazardous voltage.
Will cause death or serious
injury.
Turn off and lock out all power
supplying this device before
removing cover or device and while
cover is removed.
Replace the cover before power
supplying this device is turned on.
Page
3 of 4
Pc. No.
77503A03
Catalog
Number
Wire
Range
Torque
Cable
Clamping
Screw
Connector
Mounting
Screw
in-lbs.
N-m
in-lbs.
N-m
TC1J6600
TA1L6750
TC2J6500
TA2J6500
CCL600
3/0-500 kcmil. Cu Only
500-600 kcmil. Cu
500-750 kcmil. Al
3/0-500 kcmil. Cu Only
3/0-500 kcmil. Cu
4/0-500 kcmil. Al
(See Instructions)
500
500
500
300
300
300
56.49
56.49
56.49
33.89
33.89
33.89
228
228
228
132
132
132
25.76
25.76
25.76
14.91
14.91
14.91
TABLE 1.
7. After mounting the device, line and load terminals and
accessory terminals should be connected.
8. After the device is installed, check all mounting hard-
ware for secureness. Check wire connectors for cor-
rect torque requirements. Torque values for line and
load connectors are provided on the device nameplate
and in TABLE 1.
9. Replace line and load terminal shields and tighten
screws securely.
7.
Sólo después de instalado el interruptor, debe conectarse la
línea de alimentación, la salida a la carga y los accesorios.
8.
Después de que el interruptor esté instalado, revise todos
los elementos de conexión. Revise los conectores de cables y
observe el adecuado par de apriete, los de la línea y de la
carga, indicado en la placa de características del
interruptor.(Vea table 1)
9