3 Operation of devices
03.04.2006
3
Operation of devices
3.1
Product range
The RMZ792 bus operator unit is used for operating the following devices of the
Synco™ family (situation February 2006):
Type of unit
Type reference
Data Sheet no.
Central control unit
RMB795…
N3121
Heating controllers
RMH760…
N3131 and N3133
Boiler sequence controller
RMK770…
N3132
Switching and monitoring device
RMS705…
N3123
Universal controllers
RMU710…
RMU720…
RMU730…
N3144
N3144
N3144
Room controllers RXB…
RXB21.1/FC-09
RXB21.1/FC-10
RXB21.1/FC-11
RXB22.1/FC-08
RXB22.1/FC-12
N3872
N3873
N3873
N3872
N3873
Room controllers RXL…
RXL21.1/FC-10
RXL21.1/FC-11
RXL22.1/FC-12
N3877
N3877
N3877
Room unit for
Synco™ 700 controller
QAW740
N1633
Central communication units
OZW771…
OZW775…
N3117
N5663
To ensure trouble-free functioning of the bus operator unit, compatible software versions
of the different types of communicating units must be combined. For compatible units and
versions, refer to document J3100 (Synco™ 200 / Synco™ 700 Valid Version Set).
3.2
Remote operation and local operation
The bus operator unit provides access to the datapoints of the bus users’ user
and service levels. But the datapoints of the bus users’ password level are to be
accessed via the local RMZ790 and RMZ791 operator units. For this reason, the
RMZ792 bus operator unit cannot be used for configuring and commissioning
plant.
3.3
Navigating on the device list
During commissioning, the device list (list containing all bus users) is generated. Data-
points are always to be accessed via the device list – with the exception of the favorite
pages (refer to section 3.4 “Quick access with favorites”). By selecting the required unit
from the device list, the operator reaches the menu tree of the unit needed.
Menu tree and navigation are not any different from local operation with the
RMZ790 or RMZ791.
When pressing the INFO button during navigation, the following information is displayed: