79/88
Siemens Synco
900
CE1C2707en
Building Technologies
System limits
05.07.2007
Data backup
The current commissioning data can be saved, including the date and
the year. The data saved or the factory settings can be retrieved, if
required.
Main menu > Data backup > Storage date
(read only):
Main menu > Data backup > Storage year
(read only):
Main menu > Data backup > Restore:
Main menu > Data backup > Save:
Main menu > Data backup > Restore factory setting:
When saving the new data, any data previously saved in the
backup storage is overwritten (cannot be retrieved).
When restoring data or the factory settings, the current data
set in the device’s main storage is overwritten (cannot be
retrieved).
When restoring data, certain bus settings and all texts set are
not overwritten and are therefore retained with their present
state. When restoring the factory settings, customized texts
are also reset.
System limits
System limitations (TP1 bus)
126 Central apartment units QAX910
Limitations per central apartment unit
1 Meteo
sensor
12 Rooms
2
Door contacts (monitored)
4
Light actuators with status indication (only on KNX TP1(S-Mode))
3 RF
repeaters
64
RF devices (total number, including the central apartment unit)
In addition to the above mentioned devices, switch, dim and
blind actuators can be used in unlimited numbers.
Limitations per room
1 Room
unit
2
Room temperature sensor
1
Heating circuit controller
6
Radiator control actuators
(one lead controller, 0…5 lag controllers)
or heating circuit controller channels
6 Window
contacts
1 Smoke
detector
Radiator control actuators and heating circuit controllers can-
not simultaneously be used in the same room.
Содержание Synco 900
Страница 1: ...Synco 900 Mounting and commissioning Edition 2 0 Controller series B CE1C2707en 05 07 2007 ...
Страница 2: ......
Страница 84: ...84 88 Siemens Synco 900 CE1C2707en Building Technologies 05 07 2007 ...
Страница 85: ...85 88 Siemens Synco 900 CE1C2707en Building Technologies 05 07 2007 ...
Страница 86: ...86 88 Siemens Synco 900 CE1C2707en Building Technologies 05 07 2007 ...
Страница 87: ......