64/88
Siemens Synco
900
CE1C2707en
Building Technologies
Function settings
05.07.2007
This message is displayed if
invalid settings have been made.
Press the
Esc
or
Menu/ok
button
to return to the ”Commissioning”
menu. The plant remains out of
operation.
Function settings
General
To make function settings, you need to be on the expert level (refer to
page 15).
Change these settings only if you are fully aware of their
impact. Wrong settings can impair or even disable plant
operation.
Buzzer volume
The volume of the buzzer (piezzo loudspeaker) integrated in the central
apartment unit can be adjusted to suit individual needs (0..100 %).
Main menu > Settings > Device > Buzzer volume:
Guide value
100 %
Your setting
If the buzzer volume is too low, the acoustic signals (e.g. those
of the binding test) may not reach your ear.
Password expert level
The unit is supplied with password “9“ for accessing expert level. For
safety reasons, change the password to some other value.
When you change the password, write it down and keep it in
a safe place. If you forget your password, a service visit by
the expert is required!
Enter the required new password (between 0 and 9999) using the
following path and confirm it by pressing the
Menu/ok
button.
Main menu > Settings > Passwords > Expert:
Factory setting
9
Your setting
Caution!
Invalid settings
Start not possible
Содержание Synco 900
Страница 1: ...Synco 900 Mounting and commissioning Edition 2 0 Controller series B CE1C2707en 05 07 2007 ...
Страница 2: ......
Страница 84: ...84 88 Siemens Synco 900 CE1C2707en Building Technologies 05 07 2007 ...
Страница 85: ...85 88 Siemens Synco 900 CE1C2707en Building Technologies 05 07 2007 ...
Страница 86: ...86 88 Siemens Synco 900 CE1C2707en Building Technologies 05 07 2007 ...
Страница 87: ......