Siemens Industry, Inc.

 

 

 

G, G0: 24 Vac operating 
 

voltage 

       Y: *0 to 10 Vdc control 
 

signal 

       G: System potential 
     G0: System neutral 
     R1: 500 ohm resistor             
 

(optional for 0-20 mA 

 

operation)

 

 
 

Figure 10.   

SSC61U, NSR and SSC61.5U, SR,  

0 to 10 Vdc Proportional Control Wiring Diagram. 

 

Start-up 

Check the wiring and the position indicator (Figure 11).  

Position 

Indicator 

Output 

Shaft 

 

Retracted 

Extended 

 
NOTE:  
0

 and 

1

 markings are 

intended for reference only, 
and not stroke 
measurement. 

Figure 11.  Position Indicator (Shown in 0 Position).  

 

 

Troubleshooting 

Check the wiring for the proper connections. 

 

 
 

References 

Technical Instructions 

Document No.  

EA 599-15 Powermite 599 Series SSC 
Electronic Valve Actuator 24 Vac 
Proportional Control 

155-313P25 

EA 599-16 Powermite 599 Series SSC 
Electronic Valve Actuator  
3-position (Floating) Control  

155-314P25 

TB251, Powermite 599 Series, MT Series 
Terminal Unit Valve and Actuator Assembly 
Selection  

155-306P25 

 
 
 
 
 
 
 

 

*4 to 20 mA with 

optional 

resistor 

Содержание SSC Series

Страница 1: ...NG 1 If mounting the actuator to a valve already in line either close the shut off in the piping upstream first then downstream or switch off the pump to allow the differential pressure in the valve to drop 2 Disconnect the controller power before replacing the actuator 3 If high voltage cable is co located with the SSC actuator conduit or shielded wire may need to be used CAUTION Before applying ...

Страница 2: ...ficient cable to complete wiring terminations b Insert plenum cable adapter into flex conduit adapter and secure in place with wiring retention screw NOTE Insert wiring retention screw in hole of the flex conduit adapter The hole nearest the wiring terminals is to secure the terminal cover in place c Continue with Step 8 7 For 3 8 inch flex conduit applications complete wiring as follows a Discard...

Страница 3: ...supply transformer rating by summing the total VA of all actuators used The maximum rating for a Class 2 step down transformer is 100 VA Do not power more than 10 actuators with one transformer Use 0 5 amp on secondary actuators Y2 Retracts actuator shaft Y1 Extends actuator shaft G System potential Figure 6 SSC81U NSR Floating Control Figure 7 For Non Triac Driven Controllers Figure 8 For Triac D...

Страница 4: ...Output Shaft 0 Retracted 1 Extended NOTE 0 and 1 markings are intended for reference only and not stroke measurement Figure 11 Position Indicator Shown in 0 Position Troubleshooting Check the wiring for the proper connections References Technical Instructions Document No EA 599 15 Powermite 599 Series SSC Electronic Valve Actuator 24 Vac Proportional Control 155 313P25 EA 599 16 Powermite 599 Seri...

Страница 5: ...marks of their respective owners 2019 Siemens Industry Inc Siemens Industry Inc Smart Infrastructure 1000 Deerfield Parkway Buffalo Grove IL 60089 4513 USA 1 847 215 1000 Your feedback is important to us If you have comments about this document please send them to Sbt_technical editor us sbt siemens com Document No 129 253 Printed in the USA Page 5 of 5 Dimensions Figure 12 SSC Actuator Dimensions...