Appendix
124
Siemens Building Technologies
Fire Safety & Security Products
09.2008
Shunt
A zone with the shunt attribute set will be inhibited whenever a shunt type zone is opened. This provides a
mechanism to group the inhibition of zones with the opening of the shunt zone type.
Report Only
This attribute only applies to the FIRE zone type. If this attribute is set, then activation of the fire zone will only
report the activation to the central station. No alarms will be generated on site.
Open Only
This attribute only applies to the KEYARM zone type. If set then the arming state of the building will toggle on
openings only.
Fullset
Enable
This attribute only applies to the KEYARM zone type. If this attribute is set then zone activation will Fullset the
system/area. Apply this attribute if it is intended that the user should only have the ability to FULLSET the
system from a Keyarm zone.
Unset
Enable
This attribute only applies to the KEYARM zone type. If set then zone activation will Unset the system/area.
Apply this attribute if it is intended that the user should only have the ability to UNSET the system from a
Keyarm zone.
Keyarm
Fullset
This attribute only applies to the KEYARM zone type. If set then zone activation will Fullset the system/area.
Keyarm
Unset
This attribute only applies to the KEYARM zone type. If set then zone activation will Unset the system/area.
Tech Zone
Report
This attribute controls a dedicated tech zone output. When a tech zone changes state, the tech zone output
will follow.
That means; when the tech zone opens, then the trigger for the programmed output goes "ON" and when the
tech zone closes, then the trigger for the output goes "OFF".
NOTE
If more than one tech zone has been assigned to an area or to a system, the tech zone
output will remain on until all tech zones are closed.
Tech Zone
Display
This attribute displays an alert on a keypad plus the LED
System Alert
. This alert is only shown in "unset
mode".
NOTE
The keypad has to be assigned in the same area as the Tech Zone, otherwise the alert will
not be displayed.
Tech Zone
Audible
This attribute activates the buzzer on the keypad. The buzzer has to be enabled on the keypad and the area
has to be in "unset mode".
NOTE
The keypad has to be assigned in the same area as the Tech Zone, otherwise the buzzer
will not be activated.
Tech Zone
Delay
This attribute delays all Tech Zones (Report/Display/Audible) for the dedicated zone. If the variable delay time
from 0 to 9999 seconds is elapsed, then the activation will be activated as described in the Tech Zones
(Report/Display/Audible).
NOTE
The delay time of the zone will also delay the alarm transmission to the ARC.
16.13 Appendix N: Zone Types and Assignable Attributes
The following table shows which attributes are applicable to each zone type: