PROCEDURES

 

WARNING

 

HIGH  VOLTAGES  ARE  PRESENT.    TURN  OFF  POWER 
BEFORE INSTALLATION OR SERVICING

.

 

 

The 

use 

of 

temporary 

ground  dur

i

ng 

installation  and 

maintenance  is recommended.

 

 

1) 

Insta

ll 

one washer  over the threads 

at the end of 

the SP-37 

housing

Push the washer 

up 

against  the housing

.

 

 

2) 

Choose 

a knockout 

in the load  center  that 

is 

a distance from  the backboard  that will allow 

the back  of the SP-37  to lay flat against  the backboard

.

 

 

3) 

Install 

the 

second  washer  on the threads  at the end of the SP-37  housing  from inside the 

load  center.   Install  the lock  nut so that 

i

t loosely  holds  the SP-37 

in 

place.

 

 

4) 

Use  the wood  screw  provided  to secure  the SP-37 mounting  tab 

to 

the backboard

.

 

 

5) 

Tighten 

the 

lock 

nut installed  in 

step 3 for 

snug fit.

 

 

6) 

Cut the wires  on the SP-37 to the  m

i

nimum usable 

length

. Do 

not co

il 

the 

wires as this 

greatly  reduces  SP-37 performance

.   

Also, avoid  kinks  and sharp  bends  in the wiring

.

 

 

7) 

Connect  the wires 

to 

the load center,  observing  the proper  hook-up  scheme.

 

 

8) 

The  wires must  be connected  so that there  is a fuse  or circuit breaker  between  the SP-37 
and the power  service 

line

.

 

 

HOOK  UP  SCHEMES

 

 

 

NOTE: 

1)   20 

amp maximum  current  for each  SP-37

 

               2)  

Do not use  SP-37 

in 

circuit 

with voltage 

of more 

than 120 Vrms

.

 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 