Siemens SMG 71 Скачать руководство пользователя страница 2

Auto-Shunt

Off

On

Switch S4

Closed

Open

S3 open

2

3

4

+5

-6

B4+

1

D0

D0

D1

Reader 1

Wiegand

ABA ANSI Track 2

Reader 2

SMG 71

D1

+12V

0V

S3 close

2

3

4

+5

-6

B4+

1

CLK

CLK

DATA

Reader 1

CLK and Data can be either
open collectors, 5 V or 12 V signals

D0 and D1 can be either
open collectors, 5V or 12 V signals

Reader 2

SMG 71

DATA

+12V

0V

Type of card reader

Wiegand (26 bits)

ABA track 2 (Data + clock)

Switch S3

Closed

Open

4k7

4k7

Z

Tamper

Alarm

4k7

Z

Z

Z

Input modes

1. Normally open contact

Closed

Input

Z1
Z2

SW 1
SW 2

Open

Switch

2. Normally closed contact

3. Normally closed contact

monitored

4. Alarm & tamper monitored

5. Glass break sensor

6. Emergency exit

7. Fire input

4k7

4k7

Z

Tamper

Reset

Alarm

Z

4k7

Alarm

Trouble

Switches SW 1 and SW 2 must be open.

To connect a maximum
of 20 glass break sensor

All other modes

Z

O

4k7

The right to make technical changes to the described equipment without prior notice 

is reserved.

4.2 Tamper  contact

The Tamper connector (fi g. 1; 

T

) must be connected to an 

external tamper contact or be short-circuited.

4.3 Inputs (fi g. 4)

All inputs can be operated in modes 1 to 4 and 6 to 7 (fi g. 4). 
Inputs 1 to 2 can also be operated with glass break alarms. 
To do this, the relevant switches S1 to S2 must be closed 
and one terminal of each glass break detectors connected 
to one of outputs 1 or 2, which must be programmed for 
«Latching sensor reset». When wiring fi re detectors, any 
trouble output present can be looped directly into the line.  
For fi re detectors where the power has to be disconnected 
to reset the alarm, the negative can be connected via 
an output which is programmed as a «Latching sensor 
reset» output.
The emergency exit has to be wired like mode 6. A short 
circuit of the input will reset the corresponding signalling 
output.

4.4 Card reader (fi g. 5)

Two type of card readers (ABA Track 2 / Wiegand )  can be 
selected by the switch S3 .

5. Addressing

Since the replaced transponder takes the same address as 
the card reader gateway only free transponder addresses 
are accepted as gateway addresses.  

6. Card reader Test menu

A special menu is available in the Engineer menu to test 
the card reader.
The Site code and user number are displayed on the 
keypad.

7. Special function

7.1 Stand alone mode (fi g. 6)

In the stand alone mode, a valid card(site code) read by 
reader 1 (fi g. 1; 

p

), Will activate the relay output 1(fi g. 1; 

{

) directly for 5 seconds.

In this mode there is no interaction with the control panel, 
the site code is Checked locally in the Gateway.

7.2 Auto-Shunt mode (fi g. 7)

In the auto-shunt mode, an activation of the output 1(fi g. 1; 

{

bypasses the Input 1(fi g.1; 

O

) until it is in a quite state again.

The bypass time is max. 40 s after which the Input 1 will 
be restored.
If Input 1 is not in a quite state after 30 s the buzzer output 
(fi g.1; 

e

) will be activated.

The open collector output «Auto-Shunt function» (fi g.1; 

}

is activated as long as Input 1 is bypassed.

8. Technical  data

Supply 12 

V

DC 

from the E-Bus

Power consumption min.  

11 mA

Power consumption max. 

35 mA

7 open collector outputs  

12 V, 150 mA

1 relay output  

12 V, 1 A

4 inputs 

Programmable

8 terminating resistors  

4.7 kOhm

Operating temperature  

-10° C to +55° C

Dimensions in mm, SMG 71 

H 54,5 x W 156 x D 20

Weight, SMG 71 

65 g

Fig. 4

Fig. 5

Card reader 1

On line

Stand alone

Stand alone input (

fig. 1)

I

Closed (-)

Open

Fig. 6

Fig. 7