63
SIVACON S8 Planning Principles –
Cubicles in fixed-mounted design
2
3
4
5
6
7
8
9
10
11
1
6.3 Cubicle for customized
solutions
For individual configuration and flexible expansion of
cubicles, additional cubicles for customized solutions are
available for SIVACON S8 switchgear (Fig. 6/6). Their gen-
eral characteristics are stated in Tab. 6/13 and the configu-
ration data are described in Tab. 6/14.
Tab. 6/13:
General characteristics for cubicles for customized solutions
Application
range
- Fixed-mounted cubicle with mounting plate for individual configuration
- Use as cubicle expansion
1)
Degrees of protection
- Up to IP43
Ventilated
- IP54
Non-ventilated
Cubicle dimensions
- Cubicle height
2,000, 2,200 mm
- Cubicle width (front connection in the cubicle)
see Tab. 6/14 (cubicle design)
Device compartment
- Height
1,600, 1,800 mm
- Width
see Tab. 6/14 (cubicle design)
Form of internal separation
- Form 1, 2b
Door,
viewing door cubicle high
Design options
- Mounting plate
- ALPHA 8GK rapid mounting kits
2)
- With / without main busbar
- With / without vertical distribution busbar
1)
Expansion of cubicles to the left or right
2)
Cubicle height 2,000 mm, rear main busbar position
Fig. 6/6:
Cubicles for customized solutions
Содержание Sivacon S8
Страница 1: ...Totally Integrated Power www siemens com sivacon s8 SIVACON S8 Technical Planning Information 10 2015 ...
Страница 2: ......
Страница 6: ...Chapter 1 System based power distribution ...
Страница 23: ...20 SIVACON S8 Planning Principles SIVACON S8 System overview ...
Страница 35: ...32 SIVACON S8 Planning Principles Circuit breaker design ...
Страница 93: ...90 SIVACON S8 Planning Principles Conforming to standards and design verified ...