SIVACON S8 Planning Principles –
Universal mounting design
2
3
4
5
6
7
8
9
10
11
1
4.1 Fixed-mounted design with
compartment door
In fixed-mounted design, the switching devices are in-
stalled on mounting plates. They can be equipped with
circuit-breakers or switch-disconnectors with fuses
(Fig. 4/4; left). Tab. 4/3 gives an overview of the cubicle
characteristics in fixed-mounted design. The incoming sides
are connected to the vertical distribution busbars.
For forms 2b and 4a without current measurement, cables
are connected directly at the switching device. The maxi-
mum cross sections that can be connected are stated in the
device catalogues. For forms 3b and 4b as well as for
feeders with current measurement (transformers), the
cables are connected in the cable connection compartment
(Fig. 4/4; right). The maximum connection cross sections
are stated in Tab. 4/4.
The rating for cable feeders is stated in Tab. 4/5. The ther-
mal interaction of the feeders in the cubicle has to be and
is considered by specifying the rated diversity factor (RDF):
Permissible continuous operational current (cable feeder) =
= rated current
I
nc
x RDF
For the feeders in the cubicle, the rated diversity factor RDF
= 0.8 can be applied:
• regardless of the number of feeders in the cubicle
• regardless of the mounting position in the cubicle
For cubicles with a very high packing and/or power density,
a project-specific assessment is recommended. Further
information is available from your Siemens contact.
Tab. 4/3:
Cubicle characteristics for the fixed-mounted design
Application range
- Incoming feeders up to 630 A
- Outgoing cable feeders up to 630 A
Form of internal
separation
- Form 2b
Functional
compartment door
- Form 3b, 4a, 4b
1)
Compartment
door
Mounting designs
- Fixed-mounted module in compartment
- Empty compartment, device compartment
1)
Also form 4b type 7 in acc. with BS EN 61439-2 possible
Fig. 4/4:
Equipment in fixed-mounted design (left) and connection
terminals in the cable connection compartment (right)
Tab. 4/4:
Connection cross sections in fixed-mounted cubicles with
a front door
Nominal feeder current
Max. connection cross section
≤ 250 A
120 mm
2
> 250 A
240 mm
2
Tab. 4/5:
Ratings for cable feeders
Type
Nominal
device
current
Module height
Rated current
I
nc
at 35 °C ambient
temperature
3-pole
4-pole
Non-
ventilated
Ventilated
Fuse switch-disconnectors
1)
3NP1123
160 A
150 mm
-
106 A
120 A
3NP1133
160 A
150 mm
-
123 A
133 A
3NP1143
250 A
250 mm
-
222 A
241 A
3NP1153
400 A
300 mm
-
350 A
375 A
3NP1163
630 A
350 mm
-
480 A
530 A
3NP4010
160 A
150 mm
-
84 A
96 A
3NP4070
160 A
150 mm
-
130 A
142 A
3NP4270
250 A
250 mm
-
248 A
250 A
3NP4370
400 A
300 mm
-
355 A
370 A
3NP4470
630 A
350 mm
-
480 A
515 A
3NP5060
160 A
150 mm
-
130 A
142 A
3NP5260
250 A
250 mm
-
248 A
250 A
3NP5360
400 A
300 mm
-
355 A
370 A
3NP5460
630 A
350 mm
-
480 A
515 A
Switch-disconnectors with fuses
1)
3KL50
63 A
150 mm
250 mm
61 A
63 A
3KL52
125 A
250 mm
250 mm
120 A
125 A
3KL53
160 A
250 mm
250 mm
136 A
143 A
3KL55
250 A
300 mm
350 mm
250 A
250 A
3KL57
400 A
300 mm
350 mm
345 A
355 A
3KL61
630 A
450 mm
500 mm
535 A
555 A
Circuit-breakers
3RV2.1
16 A
150 mm
-
12.7 A
14.1 A
3RV2.2
40 A
150 mm
-
27 A
31.5 A
3RV2.3
52 A
150 mm
-
39 A
40.5 A
3RV1.4
100 A
150 mm
-
71 A
79 A
3VL1
160 A
150 mm
200 mm
121 A
151 A
3VL2
160 A
150 mm
200 mm
130 A
158 A
3VL3
250 A
200 mm
250 mm
248 A
250 A
3VL4
400 A
250 mm
300 mm
400 A
400 A
3VL5
630 A
250 mm
350 mm
525 A
565 A
3VA10
100 A
150 mm
200 mm
72 A
85 A
3VA11
160 A
150 mm
200 mm
112 A
125 A
3VA12
250 A
150 mm
200 mm
232 A
246 A
3VA20
100 A
150 mm
200 mm
100 A
100 A
3VA21
160 A
150 mm
200 mm
160 A
160 A
3VA22
250 A
150 mm
200 mm
201 A
226 A
3VA23
400 A
200 mm
250 mm
350 A
400 A
3VA24
630 A
200 mm
250 mm
410 A
495 A
Device compartments (usable overall depth 310 mm)
150 mm
200 mm
300 mm
400 mm
500 mm
600 mm
1)
Rated current with fuse link = nominal device current
Содержание Sivacon S8
Страница 1: ...Totally Integrated Power www siemens com sivacon s8 SIVACON S8 Technical Planning Information 10 2015 ...
Страница 2: ......
Страница 6: ...Chapter 1 System based power distribution ...
Страница 23: ...20 SIVACON S8 Planning Principles SIVACON S8 System overview ...
Страница 35: ...32 SIVACON S8 Planning Principles Circuit breaker design ...
Страница 93: ...90 SIVACON S8 Planning Principles Conforming to standards and design verified ...