SIVACON S8 Planning Principles –
Universal mounting design
connection compartment. In the case of 4-pole feeders, the
N conductor is allocated to the phase conductors L1, L2, L3
at the back of the cubicle. Ratings are stated in Tab. 4/2.
Combination of mounting designs
The different mounting designs can be combined in a
cubicle as shown in Fig. 4/3.
Vertical distribution busbar
The vertical distribution busbars with the phase conductors
L1, L2, L3 are arranged on the left at the back of the cubi-
cle. The PE, N or PEN busbars are arranged in the cable
Distribution busbar
Profile bar
Flat copper
1)
Cross section
400 mm
2
650 mm
2
1 x (40 mm x 10 mm)
2 x (40 mm x 10 mm)
Rated current at 35 °C ambient
temperature
Ventilated
905 A
1,100 A
865 A
1,120 A
Non-
ventilated
830 A
1,000 A
820 A
1,000 A
Rated short-time withstand
current
I
cw
(1 sec)
2)
65 kA
65 kA
65 kA
65 kA
1)
Top main busbar position
2)
Rated conditional short-circuit current
I
cc
= 150 kA
Tab. 4/2:
Ratings of the vertical distribution busbar
Fig. 4/3:
Combination options for universal mounting design
SIEMENS
SIVACON
A
2,200 / 2,000 mm
Withdrawable unit design
600 mm
1,800 / 1,600* mm
600 mm
600 / 400 * mm
Withdrawable
unit design
Withdrawable
unit design
Withdrawable unit design
Withdrawable unit design
Fixed-mounted design
Fixed-mounted
design
Fixed-mounted design
Fixed-mounted design
Fixed-mounted design
In-line design, plugged
In-line design, plugged
In-line design, plugged
* Frame height 2,000 mm
Содержание Sivacon S8
Страница 1: ...Totally Integrated Power www siemens com sivacon s8 SIVACON S8 Technical Planning Information 10 2015 ...
Страница 2: ......
Страница 6: ...Chapter 1 System based power distribution ...
Страница 23: ...20 SIVACON S8 Planning Principles SIVACON S8 System overview ...
Страница 35: ...32 SIVACON S8 Planning Principles Circuit breaker design ...
Страница 93: ...90 SIVACON S8 Planning Principles Conforming to standards and design verified ...