SITRANS AS 100 – INSTRUCTION MANUAL
Page 9
Interconnection
SITRANS AS 100 Standard Temperature Version
(ST)
Extended Temperature Version (ET)
The longer the cable, the more susceptible it is to noise and earth loops. We
recommended using cable with heavy gauge conductors and good RF/electrical shielding
(copper braid rather than drain and foil). A proper junction box close to the sensor is an
ideal location not only to extend the cable, but to also to configure the wiring for high or
low sensitivity range operation.
Notes:
•
Connect shield to ground at one end only!
•
If Sensor mounting is grounded, leave cable shield disconnected
•
If Sensor mounting is not grounded, connect cable shield to ground
*Sensor range selection
high sensitivity range = green to Vsup +
low sensitivity range = green to Vsup -
or
20 to 30 V
DC supply
input
analog output
0.08 to 10 V DC
nominal
Vsup:
Vsens:
shield--tied to Sensor casing
wht
blk
grn*
blk
red
blk
-
+
-
+
*Sensor range selection
high sensitivity range = orange to Vsup +
low sensitivity range = orange to Vsup -
org
grn*
yel
brn
or
20 to 30 V
DC supply
input
analog output
0.08 to 10 V DC
nominal
Vsup:
Vsens:
shield--tied to Sensor casing
red
blk
-
+
-
+