SITRANS TH200/TH300
Operating Instructions, 06/2010, A5E00393069-03
23
Connecting
5
5.1
Safety notes on the connection
5.1.1
General safety notes on the connection
Note
To improve the resistance:
Lay signal cables separately from cables with voltages > 60 V.
Use cables with twisted wires.
Avoid getting too close to large electrical systems or use shielded cables.
Use shielded cables to ensure the full specification according to HART, revision 5.9 in
SITRANS TH300.
Use only cable entries and covers that are approved for the relevant use.
At an ambient temperature T ≥ 60°C, use heat-resistant cables approved for an ambient
temperature of at least 20 K higher.
Use cables with wires that have a maximum cross-sectional area of 2.5 mm
2
.
Содержание SITRANS T4200
Страница 7: ...Table of contents SITRANS TH200 TH300 6 Operating Instructions 06 2010 A5E00393069 03 ...
Страница 13: ...General safety notes 2 5 Precautions SITRANS TH200 TH300 12 Operating Instructions 06 2010 A5E00393069 03 ...
Страница 45: ...Commissioning 8 2 LED operating indicator SITRANS TH200 TH300 44 Operating Instructions 06 2010 A5E00393069 03 ...
Страница 71: ...Service and maintenance SITRANS TH200 TH300 70 Operating Instructions 06 2010 A5E00393069 03 ...
Страница 85: ...Spare parts and accessories SITRANS TH200 TH300 84 Operating Instructions 06 2010 A5E00393069 03 ...
Страница 88: ...Appendix A 2 Control drawing SITRANS TH200 TH300 Operating Instructions 06 2010 A5E00393069 03 87 ...
Страница 91: ...List of abbreviations B 1 Abbreviations SITRANS TH200 TH300 90 Operating Instructions 06 2010 A5E00393069 03 ...
Страница 97: ...Glossary SITRANS TH200 TH300 96 Operating Instructions 06 2010 A5E00393069 03 ...