7
7ML19985LS31
Electronics module - Operating Instructions
33997-EN-160621
4 Mounting
4.1 Mounting instructions
If the electronics module is defective, it can be replaced by the user.
In Ex applications, only instruments and electronics modules with ap-
propriate Ex approval may be used.
4.2 Mounting preparations
In general, the electronics module can be also exchanged within the
type series against an electronics with another signal output (e.g.
relay against transistor output).
If you want to use an electronics module with a different signal output,
you can download the corresponding operating instructions manual
from our homepage under Downloads.
4.3 Installation procedure
To exchange the electronics module, proceed as follows:
1. Switch off power supply
2. Unscrew the housing lid
3. Lift the opening levers of the terminals with a screwdriver
4. Pull the connection cables out of the terminals
5. Loosen the two screws with a screw driver (Torx size T10 or slot
4)
2
1
Fig. 1: Loosen the holding screws
1 Electronics module
2 Screws (2 pcs.)
6. Pull out the old electronics module
7. Compare the new electronics module with the old one. The type
label of the electronics module must correspond to that of the old
electronics module. This applies particularly to instruments used
in hazardous areas.
8. Compare the settings of the two electronics modules. Set the
adjustment elements of the new electronics module to the same
setting of the old one.
Installation procedure
Содержание Sitrans LVL200
Страница 1: ...Operating Instructions 06 2016 Vibrating Switches Electronics module Sitrans LVL200 ...
Страница 2: ...2 7ML19985LS31 Electronics module Operating Instructions 33997 EN 160621 ...
Страница 13: ...Notes 13 7ML19985LS31 Electronics module Operating Instructions 33997 EN 160621 ...
Страница 14: ...Notes 14 7ML19985LS31 Electronics module Operating Instructions 33997 EN 160621 ...
Страница 15: ...Notes 15 7ML19985LS31 Electronics module Operating Instructions 33997 EN 160621 ...