Commissioning
5.2 Calibration
SITRANS LU150
22
Operating Instructions, 03/2016, A5E34590123-AB
5.2
Calibration
The calibration of the mA output may be done such that its span will be either proportional or
inversely proportional to the material level.
Note
The 4 and 20 mA levels may be calibrated in any order.
Proportional span
Inversely proportional span
high level = 20 mA
high level = 4 mA
low level = 4 mA
low level = 20 mA
5.3
Calibration: reference method
1.
Adjust the material level (or target) to the desired distance from the sensor face.
2.
Press the “4” or “20” key (as appropriate) to view the stored distance associated with that mA
output value.
3.
Press the key a second time to set the new distance reference.
4.
After viewing or calibrating, the unit operation automatically reverts to the Run mode (6 sec).
The calibration value is referenced from the face of SITRANS LU150 sensor, in the units
displayed.
Содержание SITRANS LU150
Страница 1: ...Operating Instructions SITRANS LU150 03 2016 Edition Ultrasonic Transmitters ...
Страница 7: ...Introduction SITRANS LU150 6 Operating Instructions 03 2016 A5E34590123 AB ...
Страница 9: ...Description SITRANS LU150 8 Operating Instructions 03 2016 A5E34590123 AB ...
Страница 21: ...Connecting 4 3 Wiring connection SITRANS LU150 20 Operating Instructions 03 2016 A5E34590123 AB ...
Страница 35: ...Troubleshooting 7 1 Troubleshooting SITRANS LU150 34 Operating Instructions 03 2016 A5E34590123 AB ...
Страница 39: ...Technical data 8 7 Approvals SITRANS LU150 38 Operating Instructions 03 2016 A5E34590123 AB ...
Страница 41: ...Appendix A 1 Measurement interval SITRANS LU150 40 Operating Instructions 03 2016 A5E34590123 AB ...