background image

4/169

Siemens FI 01 · June 2015

Level Measurement

Continuous level measurement - Ultrasonic controllers

SITRANS LU AO

4

Dimensional drawings

SITRANS LU AO, dimensions in mm (inch)

Schematics

SITRANS LU AO connections

SITRANS LU AO

SITRANS LU AO

SITRANS LU AO

Lid screws 

(6 places)

Mounting holes

(accessed under lid)

4.3 mm (0.17 inch) diameter

4 places

Enclosure

Lid

Mounting screw (by customer)

Suitable location for

 conduit entrances

209

(8.2)

172 

(6.8)

16  

(0.6)

91 

(3.6)

285 

(11.2)

267 

(10.5)

_

_

_

_

_

_

_

_

_

_

+

+

+

+

+

+

+

+

+

+

Bi-polar 

Receiver

mA

output

mA

output

mA

output

mA

output

mA

output

See note 2

See note 3

See note 1

spare

Isolated 0/4 ... 20 mA out,
750 Ω load max. (typical of 10)

100/115/200/230 V AC 
50/60 Hz select 
voltage via switch

Switch is shown in OFF position.

Select appropriate voltage.

Notes:

 

1. SITRANS LU AO receiver input is non-polarized.
2. Refer to associated application device instruction manual for wiring detail. Check that the communication parameter P740 (SITRANS LU10) is ON.
3. SITRANS LU AO interconnecting cable shield should be grounded at SITRANS LU10 only. Insulate shields at junctions to prevent inadvertent 
grounding. Maximum individual loop length is 3 000 m (10 000 ft). 

L1

L2
/N

5

1

3

5

7

9

2

4

6

8

10

10

15

20

25

6

2

11

16

21

26

7

3

1

12

17

22

27

30

8

4

13

18

23

28

31

9

14

19

24

29

32

SW3

OFF

230 V

200 V

115 V

100 V

© Siemens AG 2015