Step 3: Setting up the device modules and process values
SITRANS LT500 with PROFIBUS and PROFINET in TIA Portal V16
Application examples, 04/2022, AG022322
15
3.
We have inserted:
- Level module PT1
- Volume Flow PT1
- Sensor temperature PT1
- Totalizer Volume with control (32 bit)
- Totalizer volume with control high precision (64 bit)
- Relay status
Notice we have assigned addresses to the I and Q addresses for each module. These will
be used in our TAG table.
Note
To add or change the modules, you can select a different module from the Module list.
Drag the module in to the relevant slot and enter the I or Q address depending if the
module is an input or output.
4.
Double-click on the SITRANS LT500 to show the properties of the device.
5.
In the properties window, enter the device name (in our example “LT500” and the IP
address, in our example “192.168.1.77”) however your IP address may be different due to
your local subnet settings.
6.
Click on the “network view” so we can look at the PROFIBUS DP setup.