7ML19985XR82
SITRANS LR560 (FF)
Page EN-15
m
mmmm
Englis
h
Startup
1) Launch AMS Device Manager
a)
Launch AMS Device Manager – AMS Device Manager.
b)
From Device Connection View, right click on the FF Network icon and select Rebuild
Hierarchy.
c)
If you wish to rename the device, right-click on the device icon and select Rename
from the menu, enter a new device tag, and click Enter.
d)
Double-click the device icon. The Configure/Setup menu opens at the device
Identification dialog window. At initial startup, the Block Status is Out of Service.
2) Master Reset
a)
Navigate to Configure/Setup > Resource Block > Operation and click Methods to
open the dialog window.
b)
In the General field, click Master Reset then click Next to perform a reset to factory
defaults. Click Next to accept the default reset to Factory Defaults.
c)
Click FINISH, then scan the device (see step 3).
After a master reset to factory defaults is performed, the device will reset and the LCD will
display the Quick Start Wizard until the device is configured.
3) Scan Device
Scan Device uploads parameters from the device to AMS Device Manager. This synchronizes
parameters between the device and AMS.
a)
From the menu bar, open the pull-down menu Actions – Scan Device.
b)
If you are adding a new device, configure the device via the Quick Start wizard.
Notes:
• We recommend performing a Master Reset before configuring a new device.
• RESOURCE and LTB Blocks must be in Out of Service Mode before a Master Reset can be
performed.