SITRANS LR200 with mA/HART
134
Operating Instructions, 05/2019, A5E32337676-AE
7.6
Security (6.)
7.6.1
Remote access (6.1.)
7.6.1.1
Access control (6.1.1.)
Description
Enables /disables the read/write access to parameters via remote communica-
tions.
Options
Read only
No changes are permitted via remote communications.
Read Write
Changes are permitted.
Restricted
Sets the status to Read only, with the potential for another
HART device to change this parameter only, via remote
communications.
Factory setting
Read Write
Note
If access control is changed to limit remote access, it can only be reset via the handheld
programmer.
7.6.2
Local access (6.2.)
7.6.2.1
Write protect (6.2.1.)
Description
Prevents any changes to parameters via the handheld programmer.
Options
Range: 0 to 99999
Unlock value [stored in PIN to Unlock (6.2.2.)
(Page 135)]
Lock Off
Any other value
Lock On
Note
This lock affects only the handheld programmer. A remote master can change configuration
if Access Control(6.1.1.) (Page 134) is set to allow this.
●
To turn Lock On, key in any value other than the Unlock Value stored in PIN to Unlock
●
To turn Lock Off, key in the Unlock Value stored in PIN to Unlock (6.2.2.) (Page 135).
Содержание SITRANS LR200 7ML5422
Страница 185: ...SITRANS LR200 with mA HART Operating Instructions 05 2019 A5E32337676 AE 185 B 5 4 PFTE rod antenna threaded connection ...
Страница 193: ...SITRANS LR200 with mA HART Operating Instructions 05 2019 A5E32337676 AE 193 ...
Страница 194: ...SITRANS LR200 with mA HART 194 Operating Instructions 05 2019 A5E32337676 AE ...
Страница 212: ...Index SITRANS LR200 with mA HART 212 Operating Instructions 05 2019 A5E32337676 AE ...