Dosing timeout monitoring
The dosing timeout monitoring checks whether the dosing procedure has been finished within
the configured Duration time (menu item 2.5.5.7.2 for Recipe 1). If the duration time is
exceeded, an alarm will be triggered, see Fault codes and corrective actions (Page 171).
Dosing overrun monitoring
The dosing overrun monitoring checks if the flow amount exceeds the defined Overrun value
(menu item 2.5.5.7.4 for Recipe 1). If the overrun value is exceeded, an alarm will be triggered,
see Fault codes and corrective actions (Page 171).
This function can detect a valve malfunction (non-closure) caused by a blockage, wear, etc.
8.2.9
Audit trail logging
The audit trail includes any values or settings changed by users. The audit trail is automatically
stored with information on the change as well as the time (real-time) and by which interface
(display, bus communication or USB) the change was made.
Audit trail information is logged on the SensorFlash card, as a parameter and command change
file which include below informations:
● Timestamp
● Modbus register
● Previous value
● New value
● Data type
● Interface ID
Example: 2017-06-08 13:48:05;9003;73;74;Uint8;HMI
The transmitter can log up to 100 entries in each of the audit trail log lists:
● "Parameter change log" (menu item 3.9.1)
● "FW update change log" (menu item 3.9.3)
Each audit trail list can be cleared by the user.
See also "Diagnostic log (Page 154)" (menu item 3.2.2)
8.2.10
Diagnostic log
All unacknowledged diagnostic information are listed in the "Diagnostic log" (menu item 3.2.2).
The diagnostic alarm list is default available in operating view 6.
Parameter assignment
8.2 Functions
SITRANS FC330
154
Operating Instructions, 01/2019, A5E44030648-AB
Содержание SITRANS FC330
Страница 14: ...Introduction 1 8 Notes on warranty SITRANS FC330 14 Operating Instructions 01 2019 A5E44030648 AB ...
Страница 56: ...Installing mounting 4 3 Disassembly SITRANS FC330 56 Operating Instructions 01 2019 A5E44030648 AB ...
Страница 126: ...Operating 7 2 Remote operation SITRANS FC330 126 Operating Instructions 01 2019 A5E44030648 AB ...
Страница 158: ...Parameter assignment 8 2 Functions SITRANS FC330 158 Operating Instructions 01 2019 A5E44030648 AB ...
Страница 216: ...Technical data 11 13 Pressure temperature ratings SITRANS FC330 216 Operating Instructions 01 2019 A5E44030648 AB ...
Страница 224: ...Dimension drawings 12 7 Mounting bracket dimensions SITRANS FC330 224 Operating Instructions 01 2019 A5E44030648 AB ...
Страница 236: ...HART communication B 1 Mode of operation HART function SITRANS FC330 236 Operating Instructions 01 2019 A5E44030648 AB ...
Страница 274: ...Zero point adjustment SITRANS FC330 274 Operating Instructions 01 2019 A5E44030648 AB ...
Страница 280: ...Index SITRANS FC330 280 Operating Instructions 01 2019 A5E44030648 AB ...