DIP switch settings for communication set-up
DIP switch Com‐
munication set-up
Switch 1
Switch 2
Switch 3
Switch 4
EOL active
On
On
On
On
EOL not active
On
On
Off
Off
NOTICE
Avoid DIP switch settings not mentioned in the table
DIP switch settings not mentioned in the table preceding are not allowed and may reduce
communication interface reliability.
A: Prepare the cable by stripping it at both ends.
PP
/
PP
PP
2UDQJH
<HOORZ
:KLWH
%OXH
Figure 4-1
Cable end
B: Connect wires within the sensor terminal compartment
1. Remove the lock screw and remove the lid.
2. Undo the flexible strap.
3. Disconnect the sensor connection (white plug) from the electronic.
4. Loosen the mounting screw using a TX10 Torx driver and remove the electronic from the
housing.
5. Remove the cap and the ferrule from the cable gland and slide onto the cable.
6. Push the cable through the open gland and anchor the cable shield and the wires with the
clamp bar.
7. Remove the terminal block from the electronic.
Connecting
4.2 Connecting the FC410
SITRANS FC410
Compact Operating Instructions, 05/2020, A5E39942309-AB
29