Safety, approvals, EMC
7.2 Test voltage
SITOP PSU8200 1ph
50
Manual, 11.2014, C98130-A7633-A1-3-7629
7.2
Test voltage
Figure 7-1
Test voltage diagram
Only the manufacturer can perform the type test and production test; users can also perform
the field test.
Preconditions for performing the field test:
Tests (A) & (B)
●
Connect the input terminals with one another
●
Connect the output terminals, signaling contact and PE with one another
Test (C)
●
Connect the output terminals and signaling contact with one another and measure with
respect to PE
Table 7- 1
Test voltage for 6EP3333-8SB00-0AY0 and 6EP3334-8SB00-0AY0
Test time
Prim
↔ sec (A)
Prim ↔ PE (B)
Sec ↔ PE (C)
Type test
60 s
4200 VDC
2200 VDC
700 VDC
60 s
3000 VAC
1500 VAC
500 VAC
Production test
1 s
4200 VDC
4200 VDC
500 VDC
1 s
3000 VAC
3000 VAC
350 VAC
Field test
1 s
2200 VDC
2200 VDC
500 VDC
1 s
1500 VAC
1500 VAC
350 VAC
Note:
Tripping current for DC measurement: 0 mA
Tripping current for AC measurement: <100 mA