Installation
5
WARNING
Hazard due to electric shock
Before installation or maintenance work can begin, the system's main switch must be switched
off and measures taken to prevent it being switched on again. If this instruction is not
observed, touching live parts can result in death or serious injury.
5.1
Line-side connection
The SITOP PSU8200/3800 3ph power supply is designed for connection to a 3-phase AC
line supply (TN-, TT or IT system according to IEC 60364-1) with a rated voltage of
400 - 500 V, 50 - 60 Hz.
Figure 5-1
Line supply connection
The line supply is connected using terminals L1, L2, L3 and PE (see Figure 5-1 Line supply
connection (Page 49)), and must be implemented according to IEC 60364 .
A protective device (miniature circuit breaker or circuit breaker) and a disconnection unit for
the power supply must be provided. A ground-fault circuit interrupter is not permissible
against indirect contact as the only protective measure. This applies for the complete line
supply protected by the ground-fault circuit interrupter.
Содержание SITOP PSU3800 12 V/20 A
Страница 6: ...Overview SITOP PSU8200 3800 3ph 6 Manual 05 2018 C98130 A7638 A1 6 7629 ...
Страница 52: ...Installation 5 2 Output side connection SITOP PSU8200 3800 3ph 52 Manual 05 2018 C98130 A7638 A1 6 7629 ...
Страница 84: ...Technical data 6 9 Dimension drawing SITOP PSU8200 3800 3ph 84 Manual 05 2018 C98130 A7638 A1 6 7629 ...
Страница 90: ...Safety approvals EMC 7 4 EMC SITOP PSU8200 3800 3ph 90 Manual 05 2018 C98130 A7638 A1 6 7629 ...
Страница 104: ...Applications 9 7 Battery charging with SITOP PSU3800 SITOP PSU8200 3800 3ph 104 Manual 05 2018 C98130 A7638 A1 6 7629 ...
Страница 106: ...Environment SITOP PSU8200 3800 3ph 106 Manual 05 2018 C98130 A7638 A1 6 7629 ...