Appendix
A.1 Data formats and data sets
M200D PROFIBUS/PROFINET
204
Manual, 08/2014, A5E01577426A/RS-AA/004
A.1.11
DS93 Write command
Structure of the command data set:
Byte
Content
Value / value range
Meaning
Preamble
0
Coordination
0x21
Write via acyclic bus channel (PLC)
1
Reserved
0x00
—
2
Reserved
0x00
—
3
Reserved
0x00
—
Command
4
Number of
commands
1 ... 5
Number of subsequent valid commands
5
Command 1
Command number
Optional; for meaning see the following table
6
Command 2
Command number
Optional; for meaning see the following table
7
Command 3
Command number
Optional; for meaning see the following table
8
Command 4
Command number
Optional; for meaning see the following table
9
Command 5
Command number
Optional; for meaning see the following table
Write command
Table A- 4
Assignment of command to command number and their meaning (byte 5 to 9)
Object
No.
Command
number
Command
Meaning
0
0
Reserved
No function
703
1
Trip reset
Resets and acknowledges error messages
713
2
Emergency start ON
—
714
3
Emergency start OFF
—
709
4
Automatic mode
Transition to automatic mode
(control by DP master)
710
711
712
5
Manual
local
bus
mode
Transition to manual mode. The motor starter switches to manual
bus mode or manual local mode depending on the interface via
which the command has been received.
701
6
Factory settings
Restore the factory setting of the parameters from DS131. (Only
possible in "manual" mode.)
704
7
Maximum pointer deleted
The measured values for preventive diagnostics are deleted (= 0).
702
9
Restart
Trigger restart (as after power ON), e.g. after reassignment of the
station address. (Only possible in "manual" mode.)
707
10
Parameters disabled
CPU/master ON
Parameterization by parameterizing master not possible, or its
parameters are ignored
Содержание SIRIUS M200D
Страница 2: ......
Страница 16: ...Product description 1 3 PROFIenergy M200D PROFIBUS PROFINET 16 Manual 08 2014 A5E01577426A RS AA 004 ...
Страница 24: ...Product family 2 3 Design concept M200D PROFIBUS PROFINET 24 Manual 08 2014 A5E01577426A RS AA 004 ...
Страница 90: ...Functions 3 22 Logbook M200D PROFIBUS PROFINET 90 Manual 08 2014 A5E01577426A RS AA 004 ...
Страница 118: ...Mounting connection 4 2 Connection M200D PROFIBUS PROFINET 118 Manual 08 2014 A5E01577426A RS AA 004 ...
Страница 222: ...Appendix A 2 Order numbers M200D PROFIBUS PROFINET 222 Manual 08 2014 A5E01577426A RS AA 004 ...
Страница 224: ...Correction sheet M200D PROFIBUS PROFINET 224 Manual 08 2014 A5E01577426A RS AA 004 ...
Страница 232: ...Index M200D PROFIBUS PROFINET 232 Manual 08 2014 A5E01577426A RS AA 004 ...
Страница 233: ......