Appendix
A.1 Data formats and data sets
M200D PROFIBUS/PROFINET
196
Manual, 08/2014, A5E01577426A/RS-AA/004
A.1.5
DS69 - Read process image of the inputs
Byte
Content
Value / value range
Meaning
0
Process data
DI 0.0 to DI 0.7
See table below
1
Process data
DI 1.0 to DI 1.7
See table below
2
Reserved
—
—
3
Reserved
—
—
Table A- 2
Process image of the inputs (in bytes 0 and 1)
Byte.Bit Encoding
Process data Meaning
Relevant for
0.0
Bit (1 = active) DI 0.0
Ready (automatic)
All
0.1
DI 0.1
Motor ON
All
0.2
DI 0.2
Group fault
All
0.3
DI 0.3
Group warning
All
0.4
DI 0.4
Input 1
All
0.5
DI 0.5
Input 2
All
0.6
DI 0.6
Input 3
All
0.7
DI 0.7
Input 4
All
1.0
Bit (1 = active) DI 1.0
Current motor current I
curr
[%] bit 0
All
1.1
DI 1.1
Current motor current I
curr
[%] bit 1
All
1.2
DI 1.2
Current motor current I
curr
[%] bit 2
All
1.3
DI 1.3
Current motor current I
curr
[%] bit 3
All
1.4
DI 1.4
Current motor current I
curr
[%] bit 4
All
1.5
DI 1.5
Current motor current I
curr
[%] bit 5
All
1.6
DI 1.6
Manual local mode
All
1.7
DI 1.7
Ramp mode
sRSSte/sDSSte
Содержание SIRIUS M200D
Страница 2: ......
Страница 16: ...Product description 1 3 PROFIenergy M200D PROFIBUS PROFINET 16 Manual 08 2014 A5E01577426A RS AA 004 ...
Страница 24: ...Product family 2 3 Design concept M200D PROFIBUS PROFINET 24 Manual 08 2014 A5E01577426A RS AA 004 ...
Страница 90: ...Functions 3 22 Logbook M200D PROFIBUS PROFINET 90 Manual 08 2014 A5E01577426A RS AA 004 ...
Страница 118: ...Mounting connection 4 2 Connection M200D PROFIBUS PROFINET 118 Manual 08 2014 A5E01577426A RS AA 004 ...
Страница 222: ...Appendix A 2 Order numbers M200D PROFIBUS PROFINET 222 Manual 08 2014 A5E01577426A RS AA 004 ...
Страница 224: ...Correction sheet M200D PROFIBUS PROFINET 224 Manual 08 2014 A5E01577426A RS AA 004 ...
Страница 232: ...Index M200D PROFIBUS PROFINET 232 Manual 08 2014 A5E01577426A RS AA 004 ...
Страница 233: ......