Parameter assignment
5.7 Parameterizing output 13 / 14 (output signal ON or RUN)
SIRIUS 3RW50 soft starter
Manual, 09/2019, A5E35628455002A/RS-AA/001
99
5.7
Parameterizing output 13 / 14 (output signal ON or RUN)
Application
One of these two states is output at output 13 / 14:
●
ON
●
RUN
You will find additional information in Chapters Operating principle (Page 11) and State
diagrams of the inputs and outputs (Page 71).
Use the output function ON, for instance, to implement latching if you selected pushbutton
control.
Use the Output function RUN in order, for instance, to control a line contactor connected
upstream.
Requirements
●
Control supply voltage is connected.
●
The 3RW50 soft starter does not signal any errors, the STATE / OVERLOAD LED is
extinguished.
Procedure
1.
Start programming by pressing the MODE key longer than 2 seconds until the STATE /
OVERLOAD LED flickers green.
Press and hold the MODE key.
2.
Also press the RESET / TEST key longer than 2 seconds until the LED STATE /
OVERLOAD illuminates red.
The set state of ON / RUN relay output is displayed on the SOFT TORQUE LED:
LED Soft Torque
Signal set on output 13 / 14
Flashes green
ON (factory setting)
Flickers green
RUN
3.
Release the MODE and RESET / TEST keys.
Содержание SIRIUS 3RW50
Страница 8: ...Table of contents SIRIUS 3RW50 soft starter 8 Manual 09 2019 A5E35628455002A RS AA 001 ...
Страница 38: ...Description 1 13 Support Request SIRIUS 3RW50 soft starter 38 Manual 09 2019 A5E35628455002A RS AA 001 ...
Страница 90: ...Connecting 4 11 COM connection cable SIRIUS 3RW50 soft starter 90 Manual 09 2019 A5E35628455002A RS AA 001 ...
Страница 160: ...Functions 7 12 3RW5 HMI High Feature SIRIUS 3RW50 soft starter 160 Manual 09 2019 A5E35628455002A RS AA 001 ...
Страница 184: ...Messages and diagnosis 8 11 Logbooks SIRIUS 3RW50 soft starter 184 Manual 09 2019 A5E35628455002A RS AA 001 ...
Страница 202: ...Circuit diagrams 12 1 CAx data SIRIUS 3RW50 soft starter 202 Manual 09 2019 A5E35628455002A RS AA 001 ...