3RA61/3RA62 compact starter
5.3 Functions
SIRIUS 3RA6 compact starter
System Manual, 09/2014, NEB560060102000/RS-AA/006
61
5.3.4
Shutdown on malfunction
Type of malfunction
There is a patented mechanism for detecting malfunctions, which opens the main contacts.
The following malfunctions can be detected:
●
End of service life
Worn switching contacts or switching mechanism.
(For additional information on electrical endurance, please refer to "Technical data
(Page 245)".)
●
Faults in the control electronics
Display concept
The "Malfunction" status is indicated by the following elements:
Table 5- 8
Malfunction display elements (direct starter/reversing starter)
Actuator
Mech. display
RLT 0%
Compact starter status
TRIPPED
White display
Malfunction (e.g. end of service life reached)
Eliminating malfunctions
WARNING
Compact starter malfunction!
A compact starter malfunction will cause the compact starter to shut down. Continuing to
operate the compact starter is extremely risky, as it can no longer be considered reliable.
Following a shutdown caused by a malfunction, you will need to replace the compact
starter.
Содержание Sirius 3RA6
Страница 2: ......
Страница 14: ...Introduction SIRIUS 3RA6 compact starter 14 System Manual 09 2014 NEB560060102000 RS AA 006 ...
Страница 266: ...Technical data 9 5 8US busbar adapter SIRIUS 3RA6 compact starter 266 System Manual 09 2014 NEB560060102000 RS AA 006 ...
Страница 310: ...References B 1 References SIRIUS 3RA6 compact starter 310 System Manual 09 2014 NEB560060102000 RS AA 006 ...
Страница 314: ...Glossary SIRIUS 3RA6 compact starter 314 System Manual 09 2014 NEB560060102000 RS AA 006 ...
Страница 319: ......