①
Hook the pre-assembled feeder into the upper hooking position of the motor starter protector, and swivel the feeder
to the busbar adapter.
②
Press the locking device on the contactor down with a screwdriver.
③
Push the feeder onto the DIN rail of the busbar adapter.
④
Screw the contactor tight diagonally into the mounting plate openings provided using two M4 screws.
Tightening torque: 1.2 ... 1.5 Nm
⑤
Insert the connecting cables into the corresponding main conductor terminals. Screw the main conductor terminals
tight.
Figure 7-48
Mounting on the busbar adapter (reversing starter, screw-type connection system, size S2)
Installing the vibration and shock kit
For special vibration and shock acceleration requirements, the vibration and shock kit can be
used to secure the feeder on the busbar adapter.
Mounting
7.3 Assembly and disassembly with different mounting systems
SIRIUS 3RA Load Feeders
Equipment Manual, 02/2022, A5E03656507520A/RS-AC/004
103
Содержание SIRIUS 3RA
Страница 6: ...Table of contents SIRIUS 3RA Load Feeders 6 Equipment Manual 02 2022 A5E03656507520A RS AC 004 ...
Страница 24: ...Product combinations SIRIUS 3RA Load Feeders 24 Equipment Manual 02 2022 A5E03656507520A RS AC 004 ...
Страница 26: ...Functions SIRIUS 3RA Load Feeders 26 Equipment Manual 02 2022 A5E03656507520A RS AC 004 ...
Страница 120: ...Connection SIRIUS 3RA Load Feeders 120 Equipment Manual 02 2022 A5E03656507520A RS AC 004 ...
Страница 122: ...Operation SIRIUS 3RA Load Feeders 122 Equipment Manual 02 2022 A5E03656507520A RS AC 004 ...
Страница 132: ...Technical data 11 2 Overview tables SIRIUS 3RA Load Feeders 132 Equipment Manual 02 2022 A5E03656507520A RS AC 004 ...
Страница 136: ...Types of coordination SIRIUS 3RA Load Feeders 136 Equipment Manual 02 2022 A5E03656507520A RS AC 004 ...