Functions
2.19 Undervoltage and Overvoltage Protection (optional)
SIPROTEC, 7SD5, Manual
C53000-G1176-C169-5, Release date 02.2011
362
Figure 2-172
Logic diagram of the overvoltage protection for phase voltage
Phase-to-phase overvoltage
The phase-to-phase overvoltage protection operates just like the phase-to-earth protection except that it
detects phase-to-phase voltages. Accordingly, phase-to-phase voltages which have exceeded one of the stage
thresholds
Uph-ph>
(address
3712
) or
Uph-ph>>
(address
3714
) are also indicated. Beyond this, Figure 2-
172 applies in principle.
The phase-to-phase overvoltage protection can also be blocked via a binary input
„>Uph-ph>(>) BLK“
.