2 Functions
81
SIPROTEC 4, 7SJ62/63/64 Handbuch
C53000-G1140-C147-A, Edition 07.2015
If the current exceeds the value set in address
2205
I Max
, no further restraint will
take place for the 2nd harmonic.
The lower operating limit of the restraining function amounts to 0.25 times the sec-
ondary nominal current of the fundamental harmonic (250 mA with 1 A sec. nominal
current). The blocking is thus not enabled for lower currents. This also applies to the
ground current and, if necessary, should be taken into consideration during setting of
the pickup threshold of the ground stage.
Manual Close Mode
(Phases, ground)
When a circuit breaker is closed onto a faulted line section, a high speed trip by the
circuit breaker is usually desired. For overcurrent or high-set elements the delay may
be bypassed via a “Manual Close” signal, thus resulting in instantaneous tripping. The
internal "Manual close" signal is built from the binary input signal
„>Manual Close“
(no. 561). The internal "Manual close" signal remains active as long as the binary input
signal
„>Manual Close“
is active, but at lease for 300 ms (see the following logic
diagram).To enable the device to react properly on occurrence of a fault in the phase
elements after manual close, address
1213
MANUAL CLOSE
has to be set accordingly.
Accordingly, address
1313
MANUAL CLOSE
is considered for the ground path ad-
dress. Thus, the user determines for both elements, the phase and the ground ele-
ment, what pickup value is active with what delay when the circuit breaker is closed
manually.
Figure 2-15
Manual close feature
External Control
Switch
If the manual closing signal is not from a 7SJ62/63/64 relay, that is, neither sent via
the built-in operator interface nor via a series interface, but, rather, directly from a
control acknowledgment switch, this signal must be passed to a 7SJ62/63/64 binary
input, and configured accordingly (
„>Manual Close“
), so that the element selected
for
MANUAL CLOSE
will be effective. Its alternative
Inactive
means that the element
operates as configured even with manual close.
Internal Control
Function
The manual closing information must be allocated via CFC (interlocking task-level)
using the CMD_Information block, if the internal control function is used (see Figure
2-16).
Figure 2-16
Example for manual close feature using the internal control function
Содержание siprotec SJ62
Страница 3: ...3 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 9: ...Preface 9 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 21: ...Contents 19 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 35: ...1 Introduction 33 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 365: ...2 Functions 363 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 443: ...3 Mounting and Commissioning 441 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 529: ...4 Technical Data 527 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 699: ...A Appendix 697 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 701: ...Literature 699 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 714: ...Index 712 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 715: ...Index 713 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...