3.2 Checking Connections
416
SIPROTEC 4, 7SJ62/63/64 Handbuch
C53000-G1140-C147-A, Edition 07.2015
With data cables, the connections are designated according to DIN 66020 and ISO
2110:
• TxD = Data output
• RxD = Data input
• RTS = Request to send
• CTS = Clear to send
• GND = Signal/Chassis Ground
The cable shield is to be grounded at
both ends
. For extremely EMC-prone environ-
ments, the GND may be connected via a separate individually shielded wire pair to
improve immunity to interference.
Additional Interface
(only 7SJ64)
The additional interface available only for 7SJ64 (port D) serves for signal injection of
one or two RTD-boxes. The connection is performed according to one of the connec-
tion examples given in the Appendix A.3.
Table 3-35
Assignments of the connectors to the various interfaces
1)
Pin 7 also carries the RTS signal with RS232 level when operated as RS485 Interface. Pin 7
must therefore not be connected!
Termination
The RS485 interface is capable of half-duplex service with the signals A/A' and B/B'
with a common relative potential C/C' (GND). Verify that only the last device on the bus
has the terminating resistors connected, and that the other devices on the bus do not.
The jumpers for the terminating resistors are on the interface module RS485 (see
Figure 3-22) or on the Profibus RS485 (see Figure 3-24) or with the 7SJ64 directly on
the C–CPU-2 (see Figure 3-16 and Table 3-23). The terminating resistors can also be
connected externally (e.g. to the connection module as illustrated in Figure 3-17). In
this case, the terminating resistors located on the module must be disconnected.
If the bus is extended, make sure again that only the last device on the bus has the
terminating resistors switched-in, and that all other devices on the bus do not.
Time Synchroniza-
tion Interface
It is optionally possible to process 5 V-, 12 V- or 24 V- time synchronization signals,
provided that they are carried to the inputs named in the following table.
Pin No.
RS232
RS485
PROFIBUS FMS Slave,
RS485
Modbus RS485
Ethernet
EN 100
PROFIBUS FMS Slave,
RS485
DNP3.0 RS485
1
Shield (with shield ends electrically connected)
Tx+
2
RxD
–
–
–
Tx–
3
TxD
A/A’ (RxD/TxD-N)
B/B’ (RxD/TxD-P)
A
Rx+
4
–
–
CNTR-A (TTL)
RTS (TTL level)
—
5
GND
C/C’ (GND)
C/C’ (GND)
GND1
—
6
–
–
+5 V (max. load < 100 mA)
VCC1
Rx–
7
RTS
–
–
—
8
CTS
B/B’ (RxD/TxD-P)
A/A’ (RxD/TxD-N)
B
—
9
–
–
–
–
not available
Содержание siprotec SJ62
Страница 3: ...3 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 9: ...Preface 9 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 21: ...Contents 19 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 35: ...1 Introduction 33 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 365: ...2 Functions 363 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 443: ...3 Mounting and Commissioning 441 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 529: ...4 Technical Data 527 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 699: ...A Appendix 697 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 701: ...Literature 699 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 714: ...Index 712 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 715: ...Index 713 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...