2.25 Breaker Control
358
SIPROTEC 4, 7SJ62/63/64 Handbuch
C53000-G1140-C147-A, Edition 07.2015
The following figure shows all interlocking conditions (which usually appear in the
display of the device) for three switchgear items with the relevant abbreviations ex-
plained in the previous table. All parameterized interlocking conditions are indicated.
Figure 2-127
Example of configured interlocking conditions
Control Logic using
CFC
For the bay interlocking a control logic can be structured via the CFC. Via specific
release conditions the information “released” or “bay interlocked” are available (e.g.
object "52 Close" and "52 Open" with the data values: ON / OFF).
Switching Authori-
ty (for devices with
operator panel)
The interlocking condition "Switching Authority" serves to determine the switching au-
thorization. It enables the user to select the authorized command source. For devices
with operator panel the following switching authority ranges are defined in the follow-
ing priority sequence:
• LOCAL
• DIGSI
• REMOTE
The object "Switching Authority" serves to interlock or enable LOCAL control against
remote or DIGSI commands. The devices in housing of size
1
/
2
or
1
/
1
are equipped with
key switches on the front panel. The top switch is reserved for switching authority. The
position "LOCAL" allows local commands. The position "REMOTE" enables remote
control. For devices in housing of size
1
/
3
the switching authority can be changed
between "REMOTE" and "LOCAL" in the operator panel after having entered the pass-
word or by means of CFC also via binary input and function key.
The "Switching authority DIGSI" is used for interlocking and allows commands to be
initiated using DIGSI. Commands are allowed for both a remote and a local DIGSI con-
nection. When a (local or remote) DIGSI PC logs on to the device, it enters its Virtual
Device Number (VD). The device only accepts commands having that VD (with
switching authority = OFF or REMOTE). When the DIGSI PC logs off, the VD is can-
celled.
Commands are checked for their source SC and the device settings, and compared
to the information set in the objects "Switching authority" and "Switching authority
DIGSI".
Configuration
Switching authority available
y/n (create appropriate object)
Switching authority available DIGSI
y/n (create appropriate object)
Specific device (e.g. switching
device)
Switching authority LOCAL (check for Local
status): y/n
Specific device (e.g. switching
device)
Switching authority REMOTE (check for
LOCAL, REMOTE, or DIGSI commands):
y/n
Содержание siprotec SJ62
Страница 3: ...3 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 9: ...Preface 9 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 21: ...Contents 19 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 35: ...1 Introduction 33 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 365: ...2 Functions 363 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 443: ...3 Mounting and Commissioning 441 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 529: ...4 Technical Data 527 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 699: ...A Appendix 697 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 701: ...Literature 699 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 714: ...Index 712 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 715: ...Index 713 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...