2 Functions
216
7UT613/63x Manual
C53000-G1176-C160-2
This means that a pickup will only occur if an unbalanced load of about 1.1 times the
setting value of
I2p
(address
4021
or
4022
) is present.
The corresponding time multiplier is accessible via address
4024
D I2p
.
The time multiplication factor may also be set to
∞
. If set to infinity, the pickup of this
function will be indicated but the stage will not trip after pickup. If the inverse time stage
is not required, select
140
=
UNBALANCE LOAD
in address
Definite Time
when
configuring the protection functions.
If under address
4025
I2p DROP-OUT
the
Disk Emulation
has been set, dropout
is thus produced in accordance with the dropout characteristic, as described in the
function description of the asymmetrical load protection under margin heading „Drop-
out Behaviour“.
The „Definite Time Stages
I
2
>>,
I
2
>“ as discussed above can be used in addition to the
inverse-time stage as alarm and tripping stages.
Thermal Tripping
Characteristic
In case of generators and motors, the thermal stage permits a good adjustment of the
asymmetrical load protection to the thermal load capacity of the machine due to the
asymmetrical load. The first characteristic value is the maximum permanent permissi-
ble negative sequence current. For machines of up to 100 MVA with non-salient pole
rotors, this typically amounts to a value in a range from 6 % to 8 % of the nominal
machine current, and with salient-pole rotors at least 12 %. For larger machines and
in cases of doubt, please refer to the instructions of the machine manufacturer. Set
this value under address
4031
I2>
.
As the relevant measuring location for asymmetrical load is usually assigned to the
side of the machine to be protected, a conversion of the pickup value is not required,
i.e. during permanent permissible asymmetrical load of, for example, 11% it can be set
directly under address
4031
I2>
:
I2>
= 0,11 [I/I
nSide
].
If, however, the asymmetrical load protection must be set in amps secondary during
operation, the machine values must be converted.
Example:
Machine
I
N
= 483 A
I
2perm
= 11 % (salient-pole machine)
Current transformer
500 A/5 A
results under address
4033
in the secondary value
I2>
= 0.53 [A].
This permanently permissible negative system current is simultaneously the pickup
threshold for the thermal asymmetrical load protection and also the limit for the asym-
metrical load warning stage. The delay of the warning indication can be set under
address
4033
T WARN
. Usually approx. 20 s.
The asymmetry factor
FACTOR K
(address
4034
) is a measure for the thermal stress
of the rotor. It indicates the time for which 100 % asymmetrical load are permissible
and corresponds with the permissible thermal energy loss (K = (I/I
N
)
2
· t). It is indicated
by the machine manufacturer or it can be seen on the asymmetrical load diagram of
the machine.
Содержание SIPROTEC 7UT613 series
Страница 16: ...Contents 16 7UT613 63x Manual C53000 G1176 C160 2 Literature 631 Glossary 623 Index 633 ...
Страница 30: ...1 Introduction 30 7UT613 63x Manual C53000 G1176 C160 2 ...
Страница 506: ...A Appendix 506 7UT613 63x Manual C53000 G1176 C160 2 7UT633 D E ...
Страница 508: ...A Appendix 508 7UT613 63x Manual C53000 G1176 C160 2 7UT633 P Q ...
Страница 510: ...A Appendix 510 7UT613 63x Manual C53000 G1176 C160 2 7UT635 D E ...
Страница 512: ...A Appendix 512 7UT613 63x Manual C53000 G1176 C160 2 7UT635 P Q ...
Страница 515: ...A 2 Terminal Assignments 515 7UT613 63x Manual C53000 G1176 C160 2 7UT633 B ...
Страница 516: ...A Appendix 516 7UT613 63x Manual C53000 G1176 C160 2 7UT633 B Figure A 7 General diagram 7UT633 panel surface mounting ...
Страница 517: ...A 2 Terminal Assignments 517 7UT613 63x Manual C53000 G1176 C160 2 7UT633 N ...
Страница 518: ...A Appendix 518 7UT613 63x Manual C53000 G1176 C160 2 7UT633 N Figure A 8 General diagram 7UT633 panel surface mounting ...
Страница 519: ...A 2 Terminal Assignments 519 7UT613 63x Manual C53000 G1176 C160 2 7UT635 B ...
Страница 520: ...A Appendix 520 7UT613 63x Manual C53000 G1176 C160 2 7UT635 B Figure A 9 General diagram 7UT635 panel surface mounting ...
Страница 521: ...A 2 Terminal Assignments 521 7UT613 63x Manual C53000 G1176 C160 2 7UT635 N ...
Страница 522: ...A Appendix 522 7UT613 63x Manual C53000 G1176 C160 2 7UT635 N Figure A 10 General diagram 7UT635 panel surface mounting ...
Страница 622: ...A Appendix 622 7UT613 63x Manual C53000 G1176 C160 2 ...
Страница 632: ...Literature 632 7UT613 63x Manual C53000 G1176 C160 2 ...