2.8 Unbalanced Load Protection
215
7UT613/63x Manual
C53000-G1176-C160-2
The inverse curves (see below) permit a consideration of load imbalance per unit of
time. However, especially for generators and motors a better adjustment to the pro-
tected object can be achieved with the thermal stage (see below under „Thermal Trip-
ping Characteristic“).
Inverse Time
Element
I
2p
for IEC
Characteristics
Having selected an inverse time tripping characteristic the thermal load of a machine
caused by unbalanced load can be simulated easily. Use the characteristic which is
most similar to the thermal asymmetrical load curve of the machine manufacturer.
With the IEC characteristics (address
140
UNBALANCE LOAD
=
TOC IEC
) the follow-
ing options are available at address
4026
IEC CURVE
:
•
Normal Inverse
(inverse, type A according to IEC 60255-3),
•
Very Inverse
(very inverse, type B according to IEC 60255-3),
•
Extremely Inv.
(extremely inverse, type C according to IEC 60255-3).
The characteristics and equations they are based on are listed in the „Technical Data“.
If an inverse-time characteristic is selected, it must be noted that a safety factor of
about 1.1 has already been included between the pickup value and the setting value.
This means that a pickup will only occur if an unbalanced load of about 1.1 times the
setting value of
I2p
(address
4021
or
4022
) is present.
The corresponding time multiplier is accessible via address
4023
T I2p
.
The time multiplication factor may also be set to
∞
. If set to infinity, the pickup of this
function will be indicated but the stage will not trip after pickup. If the inverse time stage
is not required, select
140
=
UNBALANCE LOAD
in address
Definite Time
when
configuring the protection functions.
If under address
4025
I2p DROP-OUT
the
Disk Emulation
is set, dropout is thus
produced in accordance with the dropout characteristic, as described in the function
description of the asymmetrical load protection under margin heading „Dropout Be-
haviour“.
The definite time stages as discussed above under „Definite Time Stages
I
2
>>,
I
2
>“
can be used in addition to the inverse-time stage as alarm and tripping stages.
Definite Time Trip-
ping
I
2p
for ANSI
Characteristics
The thermal behaviour of a machine can be closely replicated due to negative se-
quence by means of an inverse time tripping curve. Use the characteristic which is
most similar to the thermal asymmetrical load curve of the machine manufacturer.
With the ANSI characteristics (address
140
UNBALANCE LOAD
=
TOC ANSI
) the fol-
lowing is made available in address
4027
ANSI CURVE
:
•
Extremely Inv.
,
•
Inverse
,
•
Moderately Inv.
, and
•
Very Inverse
.
The characteristics and the equations they are based on are listed in the „Technical
Data“.
If an inverse-time characteristic is selected, it must be noted that a safety factor of
about 1.1 has already been included between the pickup value and the setting value.
Setting
I2>>
= 0.55 · 545 A = 300 A primary or
0.55· 545 A · (1/600) = 0.50 A secondary
Delay
T I2>>
= 1 s
Содержание SIPROTEC 7UT613 series
Страница 16: ...Contents 16 7UT613 63x Manual C53000 G1176 C160 2 Literature 631 Glossary 623 Index 633 ...
Страница 30: ...1 Introduction 30 7UT613 63x Manual C53000 G1176 C160 2 ...
Страница 506: ...A Appendix 506 7UT613 63x Manual C53000 G1176 C160 2 7UT633 D E ...
Страница 508: ...A Appendix 508 7UT613 63x Manual C53000 G1176 C160 2 7UT633 P Q ...
Страница 510: ...A Appendix 510 7UT613 63x Manual C53000 G1176 C160 2 7UT635 D E ...
Страница 512: ...A Appendix 512 7UT613 63x Manual C53000 G1176 C160 2 7UT635 P Q ...
Страница 515: ...A 2 Terminal Assignments 515 7UT613 63x Manual C53000 G1176 C160 2 7UT633 B ...
Страница 516: ...A Appendix 516 7UT613 63x Manual C53000 G1176 C160 2 7UT633 B Figure A 7 General diagram 7UT633 panel surface mounting ...
Страница 517: ...A 2 Terminal Assignments 517 7UT613 63x Manual C53000 G1176 C160 2 7UT633 N ...
Страница 518: ...A Appendix 518 7UT613 63x Manual C53000 G1176 C160 2 7UT633 N Figure A 8 General diagram 7UT633 panel surface mounting ...
Страница 519: ...A 2 Terminal Assignments 519 7UT613 63x Manual C53000 G1176 C160 2 7UT635 B ...
Страница 520: ...A Appendix 520 7UT613 63x Manual C53000 G1176 C160 2 7UT635 B Figure A 9 General diagram 7UT635 panel surface mounting ...
Страница 521: ...A 2 Terminal Assignments 521 7UT613 63x Manual C53000 G1176 C160 2 7UT635 N ...
Страница 522: ...A Appendix 522 7UT613 63x Manual C53000 G1176 C160 2 7UT635 N Figure A 10 General diagram 7UT635 panel surface mounting ...
Страница 622: ...A Appendix 622 7UT613 63x Manual C53000 G1176 C160 2 ...
Страница 632: ...Literature 632 7UT613 63x Manual C53000 G1176 C160 2 ...