4 Technical Data
306
7UM61 Manual
C53000-G1176-C127-3
4.2
Definite-Time Overcurrent Protection (I>, ANSI 50/51; I>>, ANSI
50/51/67)
Setting Ranges / Increments
Times
Dropout Ratio
Tolerances
Pickup Current I>
for I
N
= 1 A 0.05 A to 20.00 A
Increments
0.01 A
for I
N
= 5 A
0.25 A to 100.00 A
Increments
0.05 A
Pickup Current I>>
for I
N
= 1 A 0.05 A to 20.00 A
Increments
0.01 A
for I
N
= 5 A
0.25 A to 100.00 A
Increments
0.05 A
Delay times T
0.00 s to 60.00 s
or
∞
(ineffective)
Increments 0.01 s
Undervoltage Seal-In U (phase-to-phase) 10.0 V to 125.0 V
Increments 0.01V
Holding Time of Undervoltage Seal-In
0.10 s to 60.00 s
Increments 0.01 s
Directional limit line angle tolerance I>>
–90
°
el. to +90
°
el.
Increments 1
°
The set times are pure delay times.
Pickup times (without inrush restraint, with restraint add 10 ms)
I >, I>>
Current = 2
×
Pickup Value
Current = 10
×
Pickup Value
approx. 35 ms
approx. 25 ms
Dropout Times
I >, I>>
.
approx. 50 ms
Dropout ratio overcurrent I>
approx. 0.95 for I/I
N
≥
0.3
Dropout ratio overcurrent I>>
0.90 to 0.99
(Increments 0.01)
Dropout ratio undervoltage
approx. 1.05
Dropout difference
∆ϕ
2
°
electrical
Pickup current I>, I>>
for I
N
= 1 A
1 % of setting value or 10 mA
for I
N
= 5 A
5 % of setting value or 50 mA
Undervoltage Seal-In U<
1 % of setting value or 0.5 V
Delay times T
1 % or 10 ms
Directional limit lines angle
1
°
electrical
www
. ElectricalPartManuals
. com
Содержание Siprotec 7UM611
Страница 16: ...Contents 16 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 232: ...2 Functions 232 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 292: ...3 Mounting and Commissioning 292 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 410: ...A Appendix 410 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 412: ...Literature 412 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...