2 Functions
134
7UM61 Manual
C53000-G1176-C127-3
Referred to the 6.3 kV side, this results in
The secondary current of the toroidal transformer supplies to the input of the device
For a protected zone of 90 %, the protection should already operate at 1/10 of the full
displacement voltage, whereby only 1/10 of the earth fault current is generated:
In this example
3I0>
is set to 11 mA. For the displacement voltage setting, 1/10 of the
full displacement voltage is used (because of the 90% protected zone). Considering a
500 V/100 V voltage divider, this results in:
Setting value
U0>
= 10 V
The time delay must lie below the 50 A capacity time of the loading resistor, i.e. below
20 s. The overload capacity of the earthing transformer must also be considered if it
lies below that of the loading resistor.
2.21.3 Settings
2.21.4 Information List
Addr.
Parameter
Setting Options
Default Setting
Comments
5001
S/E/F PROT.
OFF
ON
Block relay
OFF
Stator Earth Fault Protection
5002
U0>
2.0 .. 125.0 V
10.0 V
U0> Pickup
5003
3I0>
2 .. 1000 mA
5 mA
3I0> Pickup
5004
DIR. ANGLE
0 .. 360
°
15
°
Angle for Direction Determination
5005
T S/E/F
0.00 .. 60.00 sec;
∞
0.30 sec
T S/E/F Time Delay
No.
Information
Type of In-
formation
Comments
5173
>S/E/F BLOCK
EM
>BLOCK stator earth fault protection
5176
>S/E/F Iee off
EM
>Switch off earth current detec.(S/E/F)
5181
S/E/F OFF
AM
Stator earth fault prot. is switch OFF
5182
S/E/F BLOCKED
AM
Stator earth fault protection is BLOCK.
5183
S/E/F ACTIVE
AM
Stator earth fault protection is ACTIVE
www
. ElectricalPartManuals
. com
Содержание Siprotec 7UM611
Страница 16: ...Contents 16 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 232: ...2 Functions 232 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 292: ...3 Mounting and Commissioning 292 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 410: ...A Appendix 410 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 412: ...Literature 412 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...