Configuration
5-38
7SJ63 Manual
C53000-G1140-C120-1
Consistency check
In addition to the sample configuration chart 1, shown in Figure 5-36, other configura-
tion sheets may exist. The contents of any particular configuration sheet is compiled
by DIGSI
®
4 into a program and processed by the protective device. For CFC charts
developed by the user, syntactic correctness can be verified by clicking the menu
command
&KDUW
, and then
&KHFN&RQVLVWHQF\
. The consistency check will deter-
mine if the modules violate conventions of various run-time levels, or any of the prin-
ciples below.
Check of functional correctness must be performed manually.
The completed CFC chart can be saved via menu item
&KDUW
, and
&ORVH
. Likewise,
the CFC chart may be reopened and edited by clicking on
&KDUW
, selecting the appro-
priate chart, and clicking on
2SHQ
.
Please be aware, certain limitations exist, because of memory space and processing
power. The limits listed in Table 5-6 are generally applicable. The limits given in Table
5-7 are relay-specific. These limits must not be exceeded because adverse effects to
the protective functionality (e.g. slower trip times) would result.
Table 5-7
Maximum Number of Modules per Process Area for SIPROTEC
®
7SJ63
The limits are monitored by the DIGSI
®
4 operating program. When 100 % of the al-
lowed memory is used, DIGSI
®
4 issues a warning message. See Figure 5-40.
Table 5-6
Maximum Number of Charts and Inputs
Limit Description
Limit
Comment
Total number of all CFC charts for all
processing areas
32
Allowable number of CFC charts in a
single processing area
16
Total number of inputs on the left
panel for all CFC charts in event-
driven process areas
100
*
)
*) If a message is used in two charts, it counts as two
.
Valid for process areas:
PLC1_BEARB (system logic)
PLC_BEARB (protective
functions)
Maximum number of different inputs
on the left panel for all CFC charts in
event-driven process areas
50
Valid for process areas:
PLC1_BEARB (system logic)
PLC_BEARB (protective
functions)
Process Area (running level)
Number of
Blocks
Comment
MW_BEARB (Meter processing)
< 100
PLC1_BEARB (Slow PLC Logic)
approx 30
Depends on the type of functional
blocks used and the number of
connections
PLC_BEARB (Fast PLC Logic)
approx 12
SFS_BEARB (Interlocking)
< 100
www
. ElectricalPartManuals
. com
Содержание siprotec 7SJ63
Страница 16: ...xiv 7SJ63 Instruction Manual C53000 G1140 C120 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 28: ...Introduction 1 12 7SJ63 Manual C53000 G1140 C120 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 112: ...SIPROTEC 4 Devices 4 38 7SJ63 Manual C53000 G1140 C120 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 346: ...Functions 6 182 7SJ63 Manual C53000 G1140 C120 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 494: ...Technical Data 10 48 7SJ63 Manual C53000 G1140 C120 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 604: ...Index Index 6 7SJ63 Instruction Manual C53000 G1140 C120 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...