Mounting and Commissioning
3.1 Mounting and Connections
SIPROTEC, 7SJ62/64, Manual
C53000-G1140-C207-2, Release date 01.2008
414
Power Supply
Table 3-12
Jumper setting of the nominal voltage of the integrated
power supply
on the processor module
C-CPU-2
1)
230 VAC only possible for release 7SJ64**-...
/CC
and higher
Live Status Contact
Table 3-13
Jumper position of the quiescent state of the
live status contact
on the C-CPU-2 processor
printed circuit board
Pickup Voltages of BI1 to BI5
Table 3-14
Jumper settings of the
Pickup Voltages
(DC voltage) of the binary inputs BI1 to BI5 on the
C-CPU-2 processor board
1)
Factory settings for devices with power supply voltages of 24 to 125 VDC
2)
Factory settings for devices with power supply voltages of 110 to 250 VDC and 115 VAC or 115 to 230 VAC
3)
Use only with pickup voltages 220 or 250 VDC
Jumper
Rated Voltage
24 to 48 VDC
60 to 125 VDC
110 to 250 VDC,
115 to 230 VAC
X51
not used
1-2
2-3
X52
not used
1-2 and 3-4
2-3
X53
not used
1-2
2-3
X55
not used
not used
1-2
not changeable
interchangeable
Jumper
Open in the quiescent state
Closed in the quiescent state
Presetting
X40
1-2
2-3
2-3
Binary Inputs
Jumper
88 VDC Pickup
176 VDC Pickup
BI1
X21
1-2
2-3
3-4
BI2
X22
1-2
2-3
3-4
BI3
X23
1-2
2-3
3-4
BI4
X24
1-2
2-3
3-4
BI5
X25
1-2
2-3
3-4
www
. ElectricalPartManuals