![Siemens SIPROTEC 7SJ62 Скачать руководство пользователя страница 406](http://html.mh-extra.com/html/siemens/siprotec-7sj62/siprotec-7sj62_manual_382149406.webp)
Mounting and Commissioning
3.1 Mounting and Connections
SIPROTEC, 7SJ62/64, Manual
C53000-G1140-C207-2, Release date 01.2008
406
Power Supply
Table 3-4
Jumper settings for the nominal voltage of the integrated
power supply
on the processor board
A–CPU to 7SJ62.../EE
Pickup Voltages of BI1 to BI3
Table 3-5
Jumper settings for the
pickup voltages
of the binary inputs BI1 to BI3 on the processor printed
circuit board A–CPU for 7SJ62.../EE
1)
Factory settings for devices with power supply voltages of 24 VDC to 125 VDC
2)
Factory settings for devices with power supply voltages of 110 VDC to 220 VDC and 115/230 VAC
Contact Mode for Binary Outputs BO1 and BO2
Table 3-6
Jumper settings for the
contact mode
of the binary inputs BI1 to BI3 on the processor printed
circuit board A–CPU for 7SJ62.../EE
Jumper
Nominal Voltage
24/48 VDC
60 to 125 VDC
110 to 250 VDC
115 to 230 VAC
X51
Not used
1-2
2-3
X52
Not used
1-2 and 3-4
2-3
X53
Not used
1-2
2-3
cannot be changed
interchangeable
Binary Inputs
Jumper
19 VDC Pickup
88 VDC Pickup
BI1
X21
L
H
BI2
X22
L
H
BI3
X23
L
H
for
Jumper
Open in quiescent state
(NO)
Closed in quiescent state
(NC)
Presetting
BO1
X41
1-2
2-3
1-2
BO2
X42
1-2
2-3
1-2
www
. ElectricalPartManuals