$SSHQGL[
6-
&*&
01 PQinv
Reverse power direction
OFF
[ ] off
ON
[ ] on
01 CB I>
Threshold circuit breaker closed
min. 0.04
I/In
max. 1.00
©©©©
01 Im
Nominal current of motor in relation to Tr.C.
min. 0.2
max. 1.2
©©©©
01 Ia
Startup current in relation to nominal current
min. 0.4
max. 20.0
©©©©
01 tStUp
Maximum startup time
min. 1.0
s
max. 360.0
©©©©
01 ThRes
Reset thermal image on startup
YES
[ ] yes
NO
[ ] no
01 T-TRP
Minimum trip command duration
min. 0.01
s
max. 32.00
©©©©
01 T-CL
Maximum close command duration
min. 0.01
s
max. 60.00
©©©©
01TINTER
Intervalltime for average measurements
15min
[ ] 15 MIN
30min
[ ] 30 MIN
60min
[ ] 60 MIN
01CYCLE
Cycle for automatic drag indicator reset
min. 1
D
max. 365/Ñ
©©©©
01START
Start of automatic drag indicator reset
min. 1
D
max. 365
©©©©
01MINUTE
Minute of day for autom. drag indicator reset
min. 0
min
max. 1439
©©©©
©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©
10 O/C PHASE - O/C PROTECTION PHASE FAULTS
10 O/Cph
O/C protection for phase faults
ON
[ ] on
OFF
[ ] off
10 Tdyn
Duration of temporary pick-up value c/o
min. 0.1
s
max. 10000.0 ©©©©