![Siemens SIPROTEC 7SD80 Скачать руководство пользователя страница 293](http://html.mh-extra.com/html/siemens/siprotec-7sd80/siprotec-7sd80_manual_382671293.webp)
Technical Data
4.2 Protection Interfaces and Connections
SIPROTEC, 7SD80, Manual
E50417-G1140-C474-A1, Release date 09.2011
293
4.2
Protection Interfaces and Connections
Differential Protection
Protection Interfaces
1)
When using multimode fiber, a monomode patch cable is used on the sending side; a multimode patch cable
is used on the receiving side (mode conditioning patch cable).
Number of devices for one protected object
(=number of ends delimited by the current transformer)
2
Connection optical fiber
Port „A“
Connection electrical
Voltage terminal „D1“ and "D2"
Connection modules for protection data interface, depending on the order variant:
Optical protection data interface:
Maximum distance monomode fiber
14.91 miles
Maximum distance multimode fiber
miles
Protocol Full
duplex
Connector type
Duplex LC connector, SFF (IEC 61754-20 standard)
Maximum baudrate
512 kbit/s
Transmission rate
min. -15 dBm
avg
max. -8 dBm
avg
Receiver sensitivity (maximum)
-31 dBm
avg
Optical wavelength
1310 nm
Optical budget
16.0 dB
Laser Class 1 according to EN 60825-1/-2
Using monomode fiber 9 µm/125 µm
Range
You should assume a path attenuation of 0.5 dB/km (0.8 dB/miles)
for monomode and multimode fiber. For multimode fiber you must
additionally take the product of the bandwidth lengths into consider-
ation.