Mounting and Commissioning
3.3 Commissioning
SIPROTEC, 7SD610, Manual
C53000-G1176-C145-6, Release date 02.2011
300
Figure 3-17
Test of the Binary Inputs and Outputs — Example
Changing the operating state
To change the operating state of a hardware component, click on the associated switching field in the
Sched-
uled
column.
Before executing the first change of the operating state the password No. 6 will be requested (if activated during
configuration). After entry of the correct password a condition change will be executed. Further state changes
remain enabled until the dialog box is closed.
Test of the Output Relays
Each individual output relay can be energized allowing a check of the wiring between the output relay of the
7SD610 and the plant, without having to generate the message that is assigned to the relay. As soon as the
first change of state for any of the output relays is initiated, all output relays are separated from the internal
device functions, and can only be operated by the hardware test function. This means, that e.g. a TRIP
command coming from a protection function or a control command from the operator panel to an output relay
cannot be executed.
Proceed as follows in order to check the output relay:
• Make sure that the switching operations caused by the output relays can be executed without any danger
(see above under DANGER!).
• Each output relay must be tested via the corresponding
Scheduled
field of the dialog box.
• Finish the testing (see margin heading below „Exiting the Procedure“), so that during further testings no un-
wanted switchings are initiated.
Test of the Binary Inputs
To test the wiring between the plant and the binary inputs of the 7SD610 the condition in the system which ini-
tiates the binary input must be generated and the response of the device checked.
To do so, open the dialog box
Hardware Test
again to view the physical position of the binary input. The pass-
word is not yet required.
Содержание SIPROTEC 7SD610
Страница 16: ...Contents SIPROTEC 7SD610 Manual C53000 G1176 C145 6 Release date 02 2011 16 ...
Страница 267: ...Functions 2 18 Command Processing SIPROTEC 7SD610 Manual C53000 G1176 C145 6 Release date 02 2011 267 ...
Страница 268: ...Functions 2 18 Command Processing SIPROTEC 7SD610 Manual C53000 G1176 C145 6 Release date 02 2011 268 ...
Страница 428: ...Appendix A 10 Measured Values SIPROTEC 7SD610 Manual C53000 G1176 C145 6 Release date 02 2011 428 ...
Страница 430: ...Literature SIPROTEC 7SD610 Manual C53000 G1176 C145 6 Release date 02 2011 430 ...
Страница 442: ...Glossary SIPROTEC 7SD610 Manual C53000 G1176 C145 6 Release date 02 2011 442 ...
Страница 448: ...Index SIPROTEC 7SD610 Manual C53000 G1176 C145 6 Release date 02 2011 448 ...