4.14 Time Overcurrent Protection
555
7SD5 Manual
C53000-G1176-C169-1
4.14 Time Overcurrent Protection
Operating Modes
Characteristics
Definite Time High Set Current Stage
Definite Time Overcurrent Stage
As emergency overcurrent protection or back-up overcurrent protection
Emergency overcurrent protection with differential
and distance protection
Effective when the differential protection system is blocked
(e.g. because of a failure of the device communication) and the
distance protection system is blocked as well, e.g. because of
a trip of the voltage transformer mcb (via binary input), a mea-
suring voltage failure or a pickup of the fuse failure monitor
Emergency overcurrent protection with differential
protection (distance protection not configured)
Effective when the differential protection system is blocked
(e.g. because of a failure of the device communication)
Emergency overcurrent protection with distance pro-
tection (differential protection not configured)
Effective when the distance protection system is blocked, e.g.
because of a trip of the voltage transformer mcb (via binary
input), a measuring voltage failure or a pickup of the fuse
failure monitor
Back-up overcurrent protection
operates independent of any events
Definite dime stages (definite)
I
Ph
>>,3
I
0
>>,
I
Ph
>, 3
I
0
>
Inverse time stages (IDMT)
I
P
, 3
I
0P
; one of the characteristics according to
Figure 4-1 to 4-3
can be selected
Pickup value
I
Ph
>> (phases)
for
I
N
= 1 A 0.10 A to 25.00 A
or
∞
(ineffective)
Increments 0.01 A
for
I
N
= 5 A 0.50 A to 125.00 A
or
∞
(ineffective)
Pickup value 3
I
0
>> (earth)
for
I
N
= 1 A 0.05 A to 25.00 A
Or
∞
(ineffective)
Increments 0.01 A
for
I
N
= 5 A 0.25 A to 125.00 A
Or
∞
(ineffective)
Pickup value
I
Ph
>> (phases)
0.00 s to 30.00 s
Or
∞
(ineffective)
Increments 0.01 s
Delay T
3
I
0
>> (earth)
0.00 s to 30.00 s
Or
∞
(ineffective)
Increments 0.01 s
Dropout Ratio
Approx. 0.95 for
I
/
I
N
≥
0.5
Pickup times (fast relays/high-speed relays)
approx. 30/25 ms
Dropout times
Approx. 30 ms
Tolerances
Currents
3 % of setting value or 1 % nominal current
Times
1 % of setting value or 10 ms
The set times are pure delay times
Pickup value
I
Ph
> (phases)
for
I
N
= 1 A 0.10 A to 25.00 A
Or
∞
(ineffective)
Increments 0.01 A
for
I
N
= 5 A 0.50 A to 125.00 A
Or
∞
(ineffective)
www
. ElectricalPartManuals
. com
Содержание siprotec 7SD5
Страница 2: ...2 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 4: ...4 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 18: ...Contents 18 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 34: ...1 Introduction 34 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 444: ...2 Functions 444 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 580: ...4 Technical Data 580 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 682: ...Literature 682 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 698: ...Index 698 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...