2.20 Circuit Breaker Failure Protection
369
7SD5 Manual
C53000-G1176-C169-1
choice is made in address
3903
1p-RETRIP (T1)
. Set this parameter to
YES
if you
wish single-pole trip for the first stage, otherwise to
NO
.
If the breaker does not respond to this trip repetition, the adjacent circuit breakers are
tripped after T2, i.e. the circuit breakers of the busbar or of the concerned busbar
section and, if necessary, also the circuit breaker at the remote end unless the fault
has been cleared.
Separate delay times can be set
• for single- or three-pole trip repetition to the local feeder circuit breaker after a
1
-
pole trip of the feeder protection
T1-1pole
at address
3904
,
• for three-pole trip repetition to the local feeder circuit breaker after
3
-pole trip of the
feeder protection
T1-3pole
(address
3905
),
• for trip of the adjacent circuit breakers (busbar zone and remote end if applicable)
T2
at address
3906
.
The delay times are set dependant on the maximum operating time of the feeder
circuit breaker and the reset time of the current detectors of the breaker failure protec-
tion, plus a safety margin which allows for any tolerance of the delay timers. Figure 2-
159 illustrates the timing of a typical breaker failure scenario. The dropout time for si-
nusoidal currents is
≤
15 ms. If current transformer saturation is anticipated, the time
should be set to 25 ms.
Figure 2-159
Time sequence example for normal clearance of a fault, and with circuit breaker
failure, using two-stage breaker failure protection
Single-stage
Breaker Failure
Protection
With single-stage operation, the adjacent circuit breakers (i.e. the breakers of the
busbar zone and, if applicable, the breaker at the remote end) are tripped after a delay
time
T2
(address
3906
) following initiation, should the fault not have been cleared
within this time.
The timers
T1-1pole
(address
3904
) and
T1-3pole
(address
3905
) are then set to
∞
since they are not needed.
However, you may use the T1-timers for single-stage protection if you wish to utilize
the facility of setting different delay times after single-pole trip and three-pole trip of the
feeder protection. In this case set
T1-1pole
(address
3904
) and
T1-3pole
(ad-
dress
3905
) separately, but address
3903
1p-RETRIP (T1)
to
NO
, to avoid a single-
pole trip to the busbar. Set
T2
(address
3906
) to
∞
or equal to
T1-3pole
(address
www
. ElectricalPartManuals
. com
Содержание siprotec 7SD5
Страница 2: ...2 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 4: ...4 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 18: ...Contents 18 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 34: ...1 Introduction 34 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 444: ...2 Functions 444 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 580: ...4 Technical Data 580 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 682: ...Literature 682 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 698: ...Index 698 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...