Technical Data
10-8
7SA522 Manual
C53000-G1176-C119-2
– Conducted interference,
150 kHz to 30 MHz
only power supply voltage
limit class B
IEC–CISPR 22
– Radio interference field strength
30 MHz to 1000 MHz
IEC–CISPR 22
limit class B
10.1.6 Mechanical Stress Tests
Vibration and
Shock During
Operation
Standards:
IEC 60255–21 and IEC 60068–2
– Vibration
sinusoidal
IEC 60255–21–1, class 2
10 Hz to 60 Hz:
±
0.075 mm amplitude
IEC 60068–2–6
60 Hz to 150 Hz:
1 g acceleration
frequency sweep rate 1 octave/min
20 cycles in 3 orthogonal axes.
– Shock
half-sine shaped
IEC 60255–21–2, class 1
acceleration 5 g, duration 11 ms,
IEC 60068–2–27
3 shocks in each direction of
3 orthogonal axes
– Seismic vibration
sinusoidal
IEC 60255–21–2, class 1
1 Hz to 8 Hz:
±
3.5 mm amplitude
IEC 60068–3–3
(horizontal axis)
1 Hz to 8 Hz:
±
1.5 mm amplitude
(vertical axis)
8 Hz to 35 Hz:
1 g acceleration
(horizontal axis)
8 Hz to 35 Hz:
0.5 g acceleration
(vertical axis)
Frequency sweep rate1 octave/min
1 cycle in 3 orthogonal axes
Vibration and
Shock During
Transport
Standards:
IEC 60255–21 and IEC 60068–2
– Vibration
sinusoidal
IEC 60255–21–1, class 2
5 Hz to 8 Hz:
±
7.5 mm amplitude
IEC 60068–2–6
8 Hz to 150 Hz:
2 g acceleration
Frequency sweep rate1 octave/min
20 cycles in 3 orthogonal axes
– Shock
half-sine shaped
IEC 60255–21–2, class 1
acceleration 15 g; duration 11 ms;
IEC 60068–2–27
3 shocks in each direction of
3 orthogonal axes
– Continuous shock
half-sine shaped
IEC 60255–21–2, class 1
acceleration 10 g; duration 16 ms;
IEC 60068–2–29
1000 shocks in each direction of
3 orthogonal axes
Содержание siprotec 7SA522
Страница 20: ...7SA522 Manual C53000 G1176 C119 2 ...
Страница 64: ...7SA522 Manual C53000 G1176 C119 2 ...
Страница 89: ...SIPROTEC 4 Devices 4 25 7SA522 Manual C53000 G1176 C119 2 Figure 4 20 CFC Logic example ...
Страница 408: ...7SA522 Manual C53000 G1176 C119 2 ...
Страница 456: ...7SA522 Manual C53000 G1176 C119 2 ...
Страница 516: ...7SA522 Manual C53000 G1176 C119 2 ...
Страница 620: ...Appendix B 48 ...