Functions
6-228
7SA522 Manual
C53000-G1176-C119-2
6.16.3 Settings
Measurement Su-
pervision
The indicated secondary current values for setting ranges and default settings refer to
I
N
= 1 A. For the nominal current 5 A the current values are to be multiplied by 5. The
values of impedance are divided by 5.
Trip Circuit
Supervision
Addr.
Setting Title
Setting Options
Default Setting
Comments
2901 MEASURE.
SUPERV
ON
OFF
ON
Measurement Supervision
2902
BALANCE U-LIMIT
10..100 V
50 V
Voltage Threshold for Balance
Monitoring
2903
BAL. FACTOR U
0.58..0.95
0.75
Balance Factor for Voltage
Monitor
2904
BALANCE I LIMIT
0.10..1.00 A
0.50 A
Current Balance Monitor
2905
BAL. FACTOR I
0.10..0.95
0.50
Balance Factor for Current Moni-
tor
2906
Σ
I THRESHOLD
0.05..2.00 A
0.10 A
Summated Current Monitoring
Threshold
2907
Σ
I FACTOR
0.00..0.95
0.10
Summated Current Monitoring
Factor
2910
FUSE FAIL MON.
ON
OFF
ON
Fuse Failure Monitor
2911
FFM U>(min)
10..100 V
30 V
Minimum Voltage Threshold U>
2912
FFM I< (max)
0.10..1.00 A
0.10 A
Maximum Current Threshold I<
2913
FFM U<max (3ph)
2..100 V
5 V
Maximum Voltage Threshold U<
(3phase)
2914
FFM Idelta (3p)
0.05..1.00 A
0.10 A
Delta Current Threshold
(3phase)
2921
T mcb
0..30 ms
0 ms
T mcb
Addr.
Setting Title
Setting Options
Default Setting
Comments
4001
FCT TripSuperv.
ON
OFF
OFF
TRIP Circuit Supervision is
4002
No. of BI
1..2
2
Number of Binary Inputs per trip
circuit
4003
Alarm Delay
1..30 sec
2 sec
Delay Time for alarm
Содержание siprotec 7SA522
Страница 20: ...7SA522 Manual C53000 G1176 C119 2 ...
Страница 64: ...7SA522 Manual C53000 G1176 C119 2 ...
Страница 89: ...SIPROTEC 4 Devices 4 25 7SA522 Manual C53000 G1176 C119 2 Figure 4 20 CFC Logic example ...
Страница 408: ...7SA522 Manual C53000 G1176 C119 2 ...
Страница 456: ...7SA522 Manual C53000 G1176 C119 2 ...
Страница 516: ...7SA522 Manual C53000 G1176 C119 2 ...
Страница 620: ...Appendix B 48 ...