6.11.4 Information overview
The most important information about automatic reclosure is briefly explained
insofar as it was not mentioned in the following lists or described in detail in the pre-
ceding text.
" (F.No. 2742) to "
“ (F.No. 2745)
The corresponding reclose cycle is blocked. If the blocking state already exists when
the automatic reclosure function is initiated, the blocked cycle is not executed and may
be skipped (if other cycles are permitted). The same applies if the automatic
reclosure function is started(running) but not busy with(inside) the cycle being
blocked. If the block signal of a cycle appears while this cycle is being executed (busy)
the automatic reclosure function is blocked dynamically; no further automatic
reclosures cycles are then executed.
" (F.No. 2889) to "
" (F.No. 2892)
The automatic reclosure function is ready for the corresponding reclosure cycle. This
information indicates which cycle will be run next. For example, external protection
functions can use this information to release accelerated or overreaching trip stages
prior to the corresponding reclose cycle.
3493
4.AR SynRequest
YES
NO
NO
Request for synchro-check after
3pole AR
3430
AR TRIP 3pole
YES
NO
NO
3pole TRIP by AR
3431
DLC or RDT
Without
Reduced Dead Time (RDT)
Dead Line Check (DLC)
Without
Dead Line Check or Reduced
Dead Time
3438
T U-stable
0.10..30.00 sec
0.10 sec
Supervision time for dead/ live
voltage
3440
U-live>
30..90 V
48 V
Voltage threshold for live line or
bus
3441
U-dead<
2..70 V
30 V
Voltage threshold for dead line
or bus
3420
AR w/ DIST.
YES
NO
YES
AR with distance protection
3421
AR w/ SOTF-O/C
YES
NO
YES
AR with switch-onto-fault over-
current
3422
AR w/ W/I
YES
NO
YES
AR with weak infeed tripping
3423
AR w/ EF-O/C
YES
NO
YES
AR with earth fault overcurrent
prot.
3424
AR w/ DTT
YES
NO
YES
AR with direct transfer trip
3425
AR w/ BackUpO/C
YES
NO
YES
AR with back-up overcurrent
Addr.
Setting Title
Setting Options
Default Setting
Comments
Содержание siprotec 7SA522
Страница 20: ...7SA522 Manual C53000 G1176 C119 2 ...
Страница 64: ...7SA522 Manual C53000 G1176 C119 2 ...
Страница 89: ...SIPROTEC 4 Devices 4 25 7SA522 Manual C53000 G1176 C119 2 Figure 4 20 CFC Logic example ...
Страница 408: ...7SA522 Manual C53000 G1176 C119 2 ...
Страница 456: ...7SA522 Manual C53000 G1176 C119 2 ...
Страница 516: ...7SA522 Manual C53000 G1176 C119 2 ...
Страница 620: ...Appendix B 48 ...