Functions
6-31
7SA522 Manual
C53000-G1176-C119-2
Negative Sequence
Current 3I
2
On long, heavily loaded lines, the earth current measurement could be overstabilized
by large currents (ref. Figure 6-15). To ensure secure detection of earth faults in this
case, a negative sequence comparison stage is additionally provided. In the event of
a single-phase fault, the negative sequence current I
2
has approximately the same
magnitude as the zero sequence current I
0
. When the ratio zero sequence current/
negative sequence current exceeds a preset ratio, this stage picks up. It is also stabi-
lized in the event of large negative sequence currents by a parabolic characteristic.
Figure 6-16 illustrates this relationship. A release by means of the negative sequence
current comparison requires a current of at least 0,2·I
N
for 3I
0
and 3 I
2
.
Figure 6-16 Characteristic of the I
0
/I
2
–stage
Neutral Displace-
ment Voltage 3 U
0
For the neutral displacement voltage recognition the displacement voltage (
) is
numerically filtered and the fundamental frequency is monitored to recognize whether
it exceeds the set threshold (
). The reset threshold is approximately
95 % of the pick-up threshold. The U
0
–criterion may be disabled by applying the
∞
set-
ting.
Logical
Combination
The current and voltage criteria supplement each other, as the displacement voltage
increases when the zero sequence to positive sequence impedance ratio is large,
whereas the earth current increases when the zero sequence to positive sequence im-
pedance ratio is smaller.
The current and voltage criteria are logically combined with an
OR-
function (Figure 6-
17). The earth fault recognition
on it’s own
does not cause a general fault detection of
the distance protection, but merely controls the further fault detection modules. It is
only alarmed in case of a general fault detection.
0.0
0
3I0>
0,5
1,0
1,5
2,0
2,5
3,0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
release
block
3I
2
I
N
3I
0
I
N
Содержание siprotec 7SA522
Страница 20: ...7SA522 Manual C53000 G1176 C119 2 ...
Страница 64: ...7SA522 Manual C53000 G1176 C119 2 ...
Страница 89: ...SIPROTEC 4 Devices 4 25 7SA522 Manual C53000 G1176 C119 2 Figure 4 20 CFC Logic example ...
Страница 408: ...7SA522 Manual C53000 G1176 C119 2 ...
Страница 456: ...7SA522 Manual C53000 G1176 C119 2 ...
Страница 516: ...7SA522 Manual C53000 G1176 C119 2 ...
Страница 620: ...Appendix B 48 ...